BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M384410
Premises: 37 WEST 12 STREET MANHATTAN BIN: 1077930     Block: 576   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 37 W 12 ST Census Tract:   63 Health Area:  5700
7J Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 05/30/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/22/2016 11:48 AM
Application Entered:   07/22/2016 Job Start Date:   07/22/2016
Last Change:   05/30/2017 Job End Date:   03/30/2017
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     05/26/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011589 Licensee Name: JOSEPH LA POINTE
Firm: 004219 Firm Name: APOLLO ELECTRIC USA, INC
Firm Phone: 212-380-1574  Firm Address: 890 BROADWAY 6 FLOOR NEW YORK NY 10003 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $153.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: J WALSH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  2/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  200A
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
007    55  18  53             
Buildings Total   55  18  53                
Total Units : 133 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/22/2016 Notice: 1 - FIRST NOTICE 04/07/2017
Power Issued: 07/22/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  APARTMENT RENOVATION NEW METER - SERVICE WORK DONE BY OTHERS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M384410
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/06/2017 04/07/2017 STP V (35) (3)
INSPECTION COMMENTS: FAIL. DID NOT CHECK KITCHEN OR BATHROOM CKTS RAN OUT TIME
 
(2) 05/26/2017 05/30/2017 TOR C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS ONLY

OBJECTION FOR APPLICATION #: M384410
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 007) BOXS NOT COVERED CLOSET 314.25
RSLV 04/06/2017 04/06/2017 05/26/2017
 
002 (999) OTHER
(FLOOR: 007) AC FED WITH FIXTURE WIRE 250.118
RSLV 04/06/2017 04/06/2017 05/26/2017
 
003 (999) OTHER
(FLOOR: 007) AC NEEDS DISCONNECT MEANS 440.11
RSLV 04/06/2017 04/06/2017 05/26/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.