BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
Building Overview Work Items |
QUANTITY |
DESCRIPTION |
SERVICE SWITCHES |
|
A. Up to 100 AMPS |
0 |
|
B. 101 Up to 200 AMPS |
0 |
|
C. 201 Up to 600 AMPS |
0 |
|
D. 601 Up to 1200 AMPS |
0 |
|
E. Over 1200 AMPS |
0 |
|
SER. ENT. & FDR COND (EACH SET) |
|
A. Up to #2 CONDUCTOR |
1 |
|
B. Over #2 to 1/0 |
0 |
|
C. Over 1/0 to 250 MCM |
0 |
|
D. Over 250 MCM |
0 |
|
PANELS |
|
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
20-1 POLE |
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
C. 3 Phase Up to 225 AMPS |
0 |
|
D. 3 Phase Over 225 AMPS |
0 |
|
ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
B. Each Additional 10 Floors Or Less |
0 |
|
BOILER CONTROLS |
0 |
|
OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
|
001 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 002)2 WIRES UNDER 1 LUG FOR NEUTRAL FEED AND AC FEED IN PANEL 110.3 |
RSLV |
01/20/2017 |
01/20/2017 |
02/17/2017 |
|
002 |
(999) |
OTHER (FLOOR: 002) NO HANDLE TIES FOR MULTI 210.4 |
RSLV |
01/20/2017 |
01/20/2017 |
02/17/2017 |
|
003 |
(111) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (ALL FLOORS) NO WORKING SPACE FOR BOTH AC DISCONNECTS 110.26 |
RSLV |
01/20/2017 |
01/20/2017 |
02/17/2017 |
|
004 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (GROUND FLOOR) NO SERVIVCE OUTLET PROVIDED FOR AC WORK 210.63 |
RSLV |
01/20/2017 |
01/20/2017 |
04/10/2017 |
|
005 |
(999) |
OTHER (FLOOR: 002)LOW VOLTAGE DOOR BELL WIRE AND TRANSFORMER IS IN THE SAME 1900 BOXWITH THE BX CABLE (725.136) |
RSLV |
02/17/2017 |
02/17/2017 |
04/10/2017 |
|
006 |
(999) |
OTHER (FLOOR: 002)AFCI NEEDED ON ALL REQUIRED CKTS (210.12) SMOKE DETECTORS, DOOR BELLOUTLET, I.T. CLOSET (210.12) |
RSLV |
02/17/2017 |
02/17/2017 |
04/10/2017 |