BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M384035
Premises: 45 MADISON AVENUE MANHATTAN BIN: 1016880     Block: 856   Lot: 24
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 51 MADISON AV Census Tract:   56
2B LEVEL (2ND BASEMENT) Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10010 Community Board:   105
DOB Cross Street(s):   EAST 26 STREET,    EAST 27 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/14/2016 Job Start Date:   07/01/2016
Last Change:   08/22/2025 Job End Date:   09/01/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     10/25/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 011809 Licensee Name: ARTHUR A GROSSMAN
Firm: 000176 Firm Name: ATLAS-ACON ELEC. SERVICE
Firm Phone: 212-741-0600  Firm Address: 283 HUDSON STREET NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,915.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53782     Submittal #: 16A0365  
Owner / Occup: DANIEL DAVITT
Owner Business Name: NY LIFE INSURANCE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  4000AMP SERVICE SWITCH
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  20  20 SETS OF 600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/14/2016 Notice: 1 - FIRST NOTICE 10/26/2017
Power Issued: 07/14/2016 Response:  

Follow-Up:
Contractor's Comments:  CON ED OUTAGE REQUIRED

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M384035
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/05/2016 08/10/2016 BUR N (60) (0) Y
INSPECTION COMMENTS: SPOKE TO SECURITY AND BUILDING MANAGER COULD NOT LOCATE ELECTRICIAN
 
(2) 11/22/2016 11/25/2016 TUR V (60) (2)
INSPECTION COMMENTS: OBJECTION FUSES NOT AS PER ADVISORY 4000AMP SWITCH , AND BOTH DOORS IN SERVICE ROOM NOT PANIC TYPE. SEE OBJECTIONS
 
(3) 12/28/2016 12/29/2016 TUR V X (35) (1)
INSPECTION COMMENTS: FUSE IS WRONG TYPE ON DRAWING IS 4000AMP KRPC WE HAVE DRAWING REV 0 (NOTE TO CONTRACTOR I CHECKED BOX IN ACELLA CALL OFFICE SHOW THE CORRECT FUSE TO REMOVE POSSIBLE)
 
(4) 10/25/2017 10/26/2017 EDB V Y (115) (3)
INSPECTION COMMENTS: SEE ATTACHMENT.

OBJECTION FOR APPLICATION #: M384035
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AM 110.2(B) FUSES IN THE 400AMP SWITCH NOT AS PER THE DRAWING
RSLV 11/22/2016 11/22/2016 10/25/2017
 
002 (999) OTHER
(CELLAR) 110.26(C)(3) DOORS IN ELECTRICAL ROOM NOT PANIC HARDWARE
RSLV 11/22/2016 11/22/2016 10/25/2017
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)110.2(B) FUSES NOT PER DRAWING IN 4000AMP SHOULD BE 4000AMP KRPC(REV0)
OPEN 12/28/2016 12/28/2016
 
004 (255) NO FUSE COORDINATION EXISTS
(SUB-CELLAR)2B : NO FUSE COORDINATION 240.12
OPEN 10/25/2017 10/25/2017
 
005 (999) OTHER
(SUB-CELLAR)2B : NO FIRE STOP IN PENETRATION OF WALL 300.21
OPEN 10/25/2017 10/25/2017
 
006 (999) OTHER
(SUB-CELLAR)2B : SERVICE SW(S) NOT PROPERLY IDENTIFYING 230.70
OPEN 10/25/2017 10/25/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.