Electrical Application Details for App #: M383766
Premises: 430 EAST 29 STREET MANHATTAN BIN: 1087989     Block: 962   Lot: 7502
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 450 E 29 ST Census Tract:   62
1,2,3,7,ROOF Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10010 Community Board:   106
Special Place Name:   NYU
DOB Cross Street(s):    1 AVENUE,    DEAD END
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/08/2016 Job Start Date:   06/20/2016
Last Change:   08/22/2025 Job End Date:   06/20/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     12/30/2016      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 012213 Licensee Name: LEONARD HARRINGTON
Firm: 003932 Firm Name: ALLAN/BRITE-WAY ELEC'L CO
Firm Phone: 646-694-8914  Firm Address: 228 EAST 45TH STREET, 9TH FL NEW YORK NY 10017 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $3,425.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53104     Submittal #: 15A0135  
Owner / Occup:
Owner Business Name: NYU ALEXANDRIA CENTER
Authorized Representative:  RAQUEL DIAZ
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  3-260A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1-1600A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  #8 #2
B. Over #2 to 1/0  1  #1/0
C. Over 1/0 to 250 MCM  3  #2/0 #4/0 #250
D. Over 250 MCM  2  #350 #500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  35  
D. 3 Phase Over 225 AMPS  8  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/08/2016 Notice: 1 - FIRST NOTICE 08/04/2016
Power Issued: 07/08/2016 Response:  

Follow-Up:
Contractor's Comments:  ADVISORY BOARD PORTION. RE:M368213

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M383766
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/04/2016 08/04/2016 CBK V (120) (3)
INSPECTION COMMENTS: FAIL
 
(2) 12/30/2016 12/30/2016 TOR J Y (66) (0)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: M383766
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 003) FUSE TYPE, AND SIZE.
OPEN 08/04/2016 08/04/2016
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 003) 2 BUS DUCK TAP BOX NOT SHOWN UN DRAWING.
RSLV 08/04/2016 08/04/2016 12/30/2016
 
003 (999) OTHER
(ROOF) BANDING JUMPER LOOP, UNDER SIZE.
RSLV 08/04/2016 08/04/2016 12/30/2016