Electrical Application Details for App #: M383706
Premises: 200 WEST 26 STREET MANHATTAN BIN: 1082532     Block: 775   Lot: 44
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 200 W 26 ST Census Tract:   91
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 10/16/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/07/2016 Job Start Date:   06/20/2016
Last Change:   10/16/2017 Job End Date:   06/20/2017
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     09/26/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012497 Licensee Name: NICHOLAS CAMPANELLA
Firm: 004213 Firm Name: JSP ELECTL CNTNG CORP
Firm Phone: 718-554-4180  Firm Address: 178 INDUSTRIAL LOOP STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $450.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   FUTURE RETAIL SPACE
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53784     Submittal #: 16A0362  
Owner / Occup: LAZAR FEYGIN
Owner Business Name: TF CORNERSTONE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 4 + New Meters 1 - Removed Meters 0 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/07/2016 Notice: 1 - FIRST NOTICE 06/02/2017
Power Issued: 07/07/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M383706
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/17/2017 03/20/2017 PHG V (60) (3)
INSPECTION COMMENTS: CONTRACTOR TO FIX APP AND PRINT TO REFLECT TRUE INSTALL. DID NOT SEE PANEL. PRIMARY LINE OVER FUSED 1200 AMP ON 3 500MCM EXISTING
 
(2) 05/19/2017 05/19/2017 MLF N (14) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO/SHOW. CALLED OFFICE ,"WILL RESCHEDULE"
 
(3) 06/02/2017 06/02/2017 GYM V R (110) (2)
INSPECTION COMMENTS: NEW OBJECTION.
 
(4) 09/26/2017 09/26/2017 HRB C R (75) (0)
INSPECTION COMMENTS: PASSED

OBJECTION FOR APPLICATION #: M383706
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) NEUTRAL AND GROUND NOT TOGETHER 250.24
RSLV 03/17/2017 03/17/2017 06/02/2017
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)PRINT AND INSTALL DO NOT MATCH. SERVICE ON PRINT AND APP. SECONDARYINSTALLED
RSLV 03/17/2017 03/17/2017 06/02/2017
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT)NO WATER GROUND NO ROD PROVIDED FOR FIRE ALARM SS 250.64 250.53
RSLV 03/17/2017 03/17/2017 06/02/2017
 
004 (999) OTHER
(BASEMENT) 30 AMP FIRE ALARM SERVICE SW. NEUTRAL NOT BONDED 250.28
RSLV 06/02/2017 06/02/2017 09/26/2017
 
005 (999) OTHER
(BASEMENT)FEEDERS OVER CURRENT PROTECTIVE DEVICE IS OF IMPROPER SIZE240.3(EXISTING 1200 AMP SW. # 3 1200 AMP FUSES 3 SETS 500 MCMFEEDERS)
RSLV 06/02/2017 06/02/2017 09/26/2017