BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M383266
Premises: 11 HUDSON YARDS MANHATTAN BIN: 1091045     Block: 702   Lot:
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 545 W 30 ST Census Tract:   99
GROUND Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):   HIGH LINE,    11 AVENUE
Status:   C - JOB IS SIGNED OFF 06/28/2019
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/24/2016 Job Start Date:   05/04/2016
Last Change:   06/28/2019 Job End Date:   02/15/2019
Appointment Status:   
Last Inspection By:   RIVERA, F       On     06/28/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011831 Licensee Name: JAMES T GIORGIO, JR
Firm: 002393 Firm Name: B & G ELECL CONTR OF NY I
Firm Phone: 718-925-6900  Firm Address: 38-22 55 STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,615.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   ART DESIGN/OTHER
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53660     Submittal #: 16A0266  
Owner / Occup: SCOTT JONES
Owner Business Name: SCIAME CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  2-4000AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  11  11 SETS OF 600MCM COPPER
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/24/2016 Notice: 1 - FIRST NOTICE 06/06/2019
Power Issued: 06/24/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M383266
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/05/2019 06/06/2019 TOR V (190) (2)
INSPECTION COMMENTS: FAIL
 
(2) 06/28/2019 06/28/2019 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000013790
 
(3) 06/28/2019 06/28/2019 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000013796

OBJECTION FOR APPLICATION #: M383266
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 011) SIZE OF FUSE AT CS-SS-11-1#5
RSLV 06/05/2019 06/05/2019 06/28/2019
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 011) FUSE TYPE AT FIRE DISCONNECT
RSLV 06/05/2019 06/05/2019 06/28/2019