BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M383082
Premises: 304 BLEECKER STREET MANHATTAN BIN: 1010020     Block: 588   Lot: 25
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 304 BLEECKER ST Census Tract:   73 Health Area:  6400
SWK Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   BARROW STREET,    GROVE STREET
Status:   A - ASSIGNED TO INSPECTOR PHG 02/27/2019 10:15 AM
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/21/2016 9:56 AM
Application Entered:   06/21/2016 Job Start Date:   06/21/2016
Last Change:   01/30/2026 Job End Date:   07/10/2016
Appointment Status:   APPOINTMENT SCHEDULED - CONFIRMATION: 0227M
Last Inspection By:   ANTOINE FLEMING       On     01/17/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 012637 Licensee Name: SANKAR C SHIL
Firm: 004479 Firm Name: GREEN POWER ELECTRIC CORP
Firm Phone: 718-445-2740  Firm Address: 74-09 37TH AVENUE 2 FLOOR #206 JACKSON HEIGHTS NY 11372 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   S3 RESIDENCE MULTIUN
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BALJINDER SINGH
Owner Business Name: EXPERT GROUP ENTERPRISE I
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SWK                     
Buildings Total                     
Total Units : 3 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/18/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALLING SIDEWALK SHED LIGHT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M383082
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/17/2019 01/18/2019 AGF V (45) (4)
INSPECTION COMMENTS: FAIL ...OBJECTIONS ISSUED .. OUTSIDE PERIMETER ; SEPARATE STRUCTURE NOT GROUNDED , ELECTRICAL CONTINUITY NOT MAINTAINED , IMC NOT SUPPORTED , OPEN KO IN ROUND FS BOX .
 
(2) ? (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application

OBJECTION FOR APPLICATION #: M383082
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(OPEN SPACE) OPEN KO IN ROUND FS BOX , ART. 110.14
RSLV 01/17/2019 01/17/2019
 
002 (999) OTHER
(OPEN SPACE) IMC NOT PROPERLY SUPPORTED , ART. 342.30
RSLV 01/17/2019 01/17/2019
 
003 (999) OTHER
(OPEN SPACE) SEPERATE STRUCTURE NOT GROUNDED , ART. 250.32
RSLV 01/17/2019 01/17/2019
 
004 (999) OTHER
(OPEN SPACE)ROMEX SLEEVED THROUGH IMC CONDUIT , NO ELECTRICAL CONTINUITY , ART.300.12
RSLV 01/17/2019 01/17/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.