Premises: 68 5 AVENUE MANHATTAN BIN: 1009618     Block: 576   Lot: 41
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 68 5TH AV Census Tract:   63 Health Area:  5700
2ND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
Special Place Name:   THE NEW SCHOOL
DOB Cross Street(s):   EAST 12 STREET,    EAST 13 STREET
Status:   C - JOB IS SIGNED OFF 10/24/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/20/2016 7:39 AM
Application Entered:   06/20/2016 Job Start Date:   06/20/2016
Last Change:   10/24/2018 Job End Date:   08/01/2016
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     10/12/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012741 Licensee Name: MICHAEL A SHEA
Firm: 003982 Firm Name: PM ELEC'L MAINTENANCE INC
Firm Phone: 212-481-9526  Firm Address: 15 EAST 40TH ST, SUITE 303 NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $51.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARIA APPELBAUM
Owner Business Name: THE NEW SCHOOL
Authorized Representative:  MARIA APPELBAUM
Relationship To Owner:   ASSIST VICE PRINCIPLE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    14  13     
Buildings Total 14  13            
Total Units : 56 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/17/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M383022
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/14/2016 10/17/2016 EDB V (45) (5)
INSPECTION COMMENTS: SEE ATTACHMENT
 
(2) 05/24/2017 05/24/2017 ATH J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-17-000006054
 
(3) 10/02/2018 10/02/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000015433
 
(4) 10/03/2018 10/03/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000015432
 
(5) 10/03/2018 10/03/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000015431
 
(6) 10/12/2018 10/12/2018 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000015638

OBJECTION FOR APPLICATION #: M383022
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 002) A/C UNIT OVER FUSED 240.3, 110.2,3
RSLV 10/14/2016 10/14/2016 10/12/2018
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 002) PANEL : K/O MISSING 110.12
RSLV 10/14/2016 10/14/2016 10/03/2018
 
003 ( 42) BUSHINGS ARE MISSING OR LOOSE
(FLOOR: 002)PANEL : RELOCATED FEEDER ( # 2 AWG ) MISSING BUSHING 300.4,11
RSLV 10/14/2016 10/14/2016 10/03/2018
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 002) RECEPTACLE OVER 1/4" FROM WALL 314.29,21
RSLV 10/14/2016 10/14/2016 10/02/2018
 
005 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(ROOF) NO OUTLET FOR A/C EQUIPMENT 210.63
RSLV 10/14/2016 10/14/2016 05/24/2017