| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (FLOOR: 002) A/C UNIT OVER FUSED 240.3, 110.2,3 |
RSLV |
10/14/2016 |
10/14/2016 |
10/12/2018 |
| |
| 002 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 002) PANEL : K/O MISSING 110.12 |
RSLV |
10/14/2016 |
10/14/2016 |
10/03/2018 |
| |
| 003 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (FLOOR: 002)PANEL : RELOCATED FEEDER ( # 2 AWG ) MISSING BUSHING 300.4,11 |
RSLV |
10/14/2016 |
10/14/2016 |
10/03/2018 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 002) RECEPTACLE OVER 1/4" FROM WALL 314.29,21 |
RSLV |
10/14/2016 |
10/14/2016 |
10/02/2018 |
| |
| 005 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT (ROOF) NO OUTLET FOR A/C EQUIPMENT 210.63 |
RSLV |
10/14/2016 |
10/14/2016 |
05/24/2017 |