Premises: 1120 5 AVENUE MANHATTAN BIN: 1047101     Block: 1505   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1120 FIFTH AV Census Tract:   160.01 Health Area:  2820
14A Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   EAST 93 STREET,    EAST 94 STREET
Status:   C - JOB IS SIGNED OFF 12/28/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/31/2016 3:49 PM
Application Entered:   05/31/2016 Job Start Date:   05/31/2016
Last Change:   12/28/2018 Job End Date:   05/31/2018
Appointment Status:   
Last Inspection By:   RIVERA, F       On     12/14/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012684 Licensee Name: STEVEN P PALMO
Firm: 004518 Firm Name: HI-TECH WIRING ELECL SVCS
Firm Phone: 212-684-5350  Firm Address: 32 EAST 31ST STREET-8TH FL NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $471.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MR AND MRS. AMIRSALEH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP FUSED DISCONNECT
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #6/3 FEEDER
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  3/0-4 WIRE
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CIRCUIT LIGHTING PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  42 CIRCUIT MAIN LUG PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
014  150  100  70               
014  14A  137  89  63               
Buildings Total 287  189  133                  
Total Units : 617 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/31/2016 Notice: 1 - FIRST NOTICE 10/30/2018
Power Issued: 05/31/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M382257
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/16/2018 10/16/2018 PHG N (25) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 10/30/2018 10/30/2018 AYC V (81) (3)
INSPECTION COMMENTS: FAIL
 
(3) 12/14/2018 12/14/2018 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000019886
 
(4) 12/14/2018 12/14/2018 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000019887
 
(5) 12/14/2018 12/14/2018 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000019954

OBJECTION FOR APPLICATION #: M382257
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 014)ART. 210.8 GFCI PROTECTION FOR THE TOILET OUTLET NOT PROVIDED.
RSLV 10/30/2018 10/30/2018 12/14/2018
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) ART. 314.28(C) TROUGHWAY MISSING COVER.
RSLV 10/30/2018 10/30/2018 12/14/2018
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) ART. 110.16 DISCONNECT SWITCH MISSING ARC FLASH LABEL.
RSLV 10/30/2018 10/30/2018 12/14/2018