Electrical Application Details for App #: M382017
Premises: 38 EAST 85 STREET MANHATTAN BIN: 1046824     Block: 1496   Lot: 54
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 38 E 85 ST Census Tract:   150.01 Health Area:  3600
12 FL APT PH Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   C - JOB IS SIGNED OFF 09/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/24/2016 10:32 AM
Application Entered:   05/24/2016 Job Start Date:   05/24/2016
Last Change:   09/14/2017 Job End Date:   03/24/2017
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     08/22/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010190 Licensee Name: ABE HIMELFARB
Firm: 002663 Firm Name: ALEF ELEC'L CONTR'G INC
Firm Phone: 212-764-2200  Firm Address: 247 WEST 38TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $117.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MADELINE PULLING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
012  PH  25  40    18  25             
Buildings Total 25  40    18  25                
Total Units : 108 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/25/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ON EXISTING RISER--REPL TWO PANELS INST 4 SD

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M382017
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/27/2017 03/27/2017 GYM N (35) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 05/24/2017 05/25/2017 PHG V (45) (4)
INSPECTION COMMENTS: CONTRACTOR TO FILE FOR ALL WORK HEATERS AC ECT DID NOT INSPECT MOTORS HEATERS
 
(3) 08/22/2017 08/23/2017 TOR C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M382017
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 012) NO GROUND IN ALL FMC FEEDING PANELS 250.118
RSLV 05/24/2017 05/24/2017 08/22/2017
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 012) NO GFCI KITCHEN ISLAND 210.8
RSLV 05/24/2017 05/24/2017 08/22/2017
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 012)RECEPTACLE IN BATHROOM/CLOSET NEED GFCI PROTECTION 210.8
RSLV 05/24/2017 05/24/2017 08/22/2017
 
004 (999) OTHER
(FLOOR: 012) FACE UP OUTLET NOT PERMITTED IN BED ROOMS 406.5
RSLV 05/24/2017 05/24/2017 08/22/2017