BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M381998
Premises: 59 WEST 12 STREET MANHATTAN BIN: 1066992     Block: 576   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 59 W 12TH ST Census Tract:   63 Health Area:  5700
APT. 4G Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 09/30/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/23/2016 6:16 PM
Application Entered:   05/23/2016 Job Start Date:   05/23/2016
Last Change:   09/30/2017 Job End Date:   06/30/2016
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     03/27/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010210 Licensee Name: MENASHE OVADIA
Firm: 003985 Firm Name: A & S MASTER ELEC'L CORP
Firm Phone: 718-361-7672  Firm Address: 47-25 27TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $85.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ABIGAIL WILLIAMS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  4G  29               
Buildings Total 29                  
Total Units : 41 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/07/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:   5-LIGHTS,5-SWITCHES,18-OUTLETS,4-GFCI OUTLETS,REPLACE ELECTRICAL PANEL W/24/30 CIRCUITS,4-KITCHEN DEDICATED LINES,3-KITCHEN COUNTER GFCI OUTLETS,2-DEDICATED LINES FOR AC OUTLETS 110V 20AMPS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M381998
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/06/2017 02/07/2017 CBK V (55) (5)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(2) 03/27/2017 03/27/2017 MLF C R (30) (0)
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: M381998
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(FLOOR: 004) SPLICE BOX IN KITCHEN MISSING KO SEALS.
RSLV 02/06/2017 02/06/2017 03/27/2017
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 004) AFCI NOT PROVIDED
RSLV 02/06/2017 02/06/2017 03/27/2017
 
003 (999) OTHER
(FLOOR: 004)MICRO-WAVE, AND ALL RECEPTACLE BOXES IN BASEBOARD SET BACK. 314.20
RSLV 02/06/2017 02/06/2017 03/27/2017
 
004 (999) OTHER
(FLOOR: 004) CIRCUITS NEED TO BE GROUP IN PANEL. 210.4
RSLV 02/06/2017 02/06/2017 03/27/2017
 
005 (999) OTHER
(FLOOR: 004) WIRES DOUBLE UP ON ONE BREAKER IN PANEL. 110.3
RSLV 02/06/2017 02/06/2017 03/27/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order