| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
6 |
200A |
| D. 3 Phase Over 225 AMPS |
2 |
800A , 600A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
02/22/2017 |
02/24/2017 |
EDB |
V |
|
|
(85) |
|
(4) |
|
| INSPECTION COMMENTS:
|
AL WIRE REPLACED WITH CU WIRE IN 1000 KVA SERVICE ROOM. NOT FINAL. SEE ATTACHMENT .
|
| |
| (2) |
11/29/2019 |
11/30/2019 |
STP |
N |
|
|
(35) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
NO SHOW. CALLED CONTRACTOR, NO ANSWER.
|
| |
| (3) |
12/11/2019 |
12/11/2019 |
AGF |
V |
X |
|
(124) |
|
(7) |
|
| INSPECTION COMMENTS:
|
FAIL ... OBJECTIONS ISSUED . PLEASE NOTE , ELECTRICAL ROOM IN UNSAFE SPACE AS WELL , DOOR DOES NOT OPEN FULLY , A WHOLE IN THE FLOOR UPON EXITING AND NO VENTILATION . ADVISORY BOARD APPROVAL NOT PROVIDED , CONTRACTOR CAME OFF THE LINE SIDE OF A 2000 AMP SERVICE SWITCH , WITH A 400 AMP DISCONNECT FUSED AT 200 AMP , OF THE 200AMP FUSE CAME (+)
|
| |
| (4) |
02/06/2020 |
02/07/2020 |
CDX |
N |
|
|
(75) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
NO SHOW. CALLED CONTRACTOR NOT COMING.
|
| |
| (5) |
02/13/2020 |
02/14/2020 |
STP |
V |
Y |
|
(120) |
|
(6) |
|
| INSPECTION COMMENTS:
|
FAIL. APP NOT PROPERLY FILED. NO VENTILATION PROVIDED FOR ELECTRICAL SPACE. COOKING FUMES GOING UP TO WHERE ALL EQUIPMENT LOCATED. WHATS APPROVED SPACE SHOWN TO BE USED AS ON APPROVED PLANS. SUPER PROVIDED ORIGINAL PLANS THAT SHOW 600 A FUSE WITH ALUMINUM CONDUCTORS. FUSE CHANGED. FEEDER DIAGRAM NOT PROVIDED.
|
| |
| (6) |
01/20/2021 |
01/20/2021 |
EDB |
J |
X |
|
(50) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
CONTRACTOR NOT READY FOR INSPECTION (NEED AB DRAWING). INSPECTION INCOMPLETE.
|
| |
| (7) |
04/20/2021 |
04/21/2021 |
STP |
J |
Y |
|
(85) |
|
(0) |
|
| INSPECTION COMMENTS:
|
FAIL. SEE PREVIOUS COMMENTS.
|
| |
| (8) |
11/23/2021 |
11/23/2021 |
AGF |
N |
|
|
(142) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
NO SHOW ... CONTRACTOR NEVER SHOWED UP ,SAID SOMEONE SHOULD BE COMING . TOLD TO STAY IN PLACE BY OFFICE .
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION (ALL FLOORS) 200 A 277/480 V FEED ENTIRE SPACE 220 |
OPEN |
02/22/2017 |
02/22/2017 |
|
| |
| 002 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (CELLAR)EL. RM. : NO WORKING SPACE IN FRONT EL. EQUIPMENT 110.26 |
OPEN |
02/22/2017 |
02/22/2017 |
|
| |
| 003 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL (CELLAR) CONTRACTOR CHANGE 2ND LEVEL FUSE IN 800 A TRANS-S TO 200 AAM. 110.2 |
OPEN |
02/22/2017 |
02/22/2017 |
|
| |
| 004 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (CELLAR) EMT NOT SECURED IN KITCHEN AREA |
OPEN |
02/22/2017 |
02/22/2017 |
|
| |
| 005 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)ELECTRICAL RM. NOT LABEL , NYC AMEND |
RSLV |
12/11/2019 |
12/11/2019 |
04/20/2021 |
| |
| 006 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)DIAGRAM OF FEEDERS SHALL BE ACCOMPANIED TO INSPECTION , ART. 215.5 |
OPEN |
12/11/2019 |
12/11/2019 |
|
| |
| 007 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)TRANSFORMER ROOM NOT FIREPROOF , NOT VENTILATION , ART. 450 |
RSLV |
12/11/2019 |
12/11/2019 |
04/20/2021 |
| |
| 008 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)ADVISORY BOARD APPROVAL FOR SECOND FUSING AFTER 2000 AMP MAIN SWITCHNOT PROVIDED , NYC AMEND |
OPEN |
12/11/2019 |
12/11/2019 |
|
| |
| 009 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)PLATE USED IN TROUG HAS A REDUCER UNDER 700 MDP NOT LISTED FOR USE, ART. 110 |
RSLV |
12/11/2019 |
12/11/2019 |
04/20/2021 |
| |
| 010 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)NO MIGB ON SET OF CONDUCTORS FEEDING 700AMP MDP , ART. 250 |
RSLV |
12/11/2019 |
12/11/2019 |
02/13/2020 |
| |
| 011 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)ELECTRICAL RM UNSAFE EGRESS , ART. 110 |
OPEN |
12/11/2019 |
12/11/2019 |
|
| |
| 012 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE (ALL FLOORS) FILE SWITCHS, FEEDERS, ETC |
OPEN |
02/13/2020 |
02/13/2020 |
|
| |
| 013 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (CELLAR) 314.29 ACCESS TO SPLICE POINT TWO SETS 350 KCMIL 277/480V |
OPEN |
02/13/2020 |
02/13/2020 |
|
| |
| 014 |
(286) |
NO GFCI IN COMMERCIAL KITCHEN (CELLAR)210.8 GREY RECEPTACLES NOT ALL GFCI/ SAID REMOVED BECAUSE TRIPPING |
OPEN |
02/13/2020 |
02/13/2020 |
|
| |
| 015 |
(137) |
GROUNDING ELECTRODE CONDUCTOR IS NOT OF PROPER SIZE FOR SERVICE (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)250.66 300 KVA TRANSFORMER GEC |
OPEN |
02/13/2020 |
02/13/2020 |
|
| |
| 016 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)240.4 300 KVA TRANSFORMER SECONDARY WIRES UNDERSIZED |
RSLV |
02/13/2020 |
02/13/2020 |
04/20/2021 |
| |
| 017 |
(273) |
GROUND CLAMP NOT ACCESSIBLE (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)250.68 GEC FOR 300 KVA TRANSFORMER |
OPEN |
02/13/2020 |
02/13/2020 |
|