| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
4 |
3-600A, 1-400A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
24 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
6 |
2 SET 500MCM,4 SET 350MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
23 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 002)RECEPTACLE NOT GFCI PROTECTED NEAR HAIR WASHING SINK 210.8 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 002 |
(999) |
OTHER (FLOOR: 008)APT 8B AND 5B RECEPTACLES NOT PLACED PROPERLY ON COUNTERTOP 210.52 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS)ALL FLRS, EXIT LIGHT FIXTURE BOXES RECESS TOO FAR BACK IN WALL314.20 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 004 |
(999) |
OTHER (CELLAR) EQUIPMENTS NOT LABEL PROPERLY 110.22 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 005 |
(999) |
OTHER (CELLAR)PLP AND OTHER PANELS SHEET METAL SCREW USED TO SECURE GROUND BARS INPANELS 250.8 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 006 |
(999) |
OTHER (CELLAR) FIRE ALARM CONDUIT NOT CONTINUOUS WITH ELECTRODE 250.64E |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 007 |
(999) |
OTHER (CELLAR) ARC FLASH STICKERS NOT PROVIDED ON EQUIPMENTS 110.16 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 008 |
(999) |
OTHER (CELLAR)FIRE PUMP DISCONNECT NOT 12 INCHES AWAY FROM SERVICE AMEN 695.4B3 |
RSLV |
05/04/2017 |
05/04/2017 |
07/20/2017 |
| |
| 009 |
(999) |
OTHER (CELLAR)DISCONNECT FOR COMMERCIAL SPACES NOT BONDED PROPERLY FOR LOAD SIDECONDUIT 250.4 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 010 |
(999) |
OTHER (CELLAR) SUMP PUMP FLEXIBLE CABLE RUNNING INSIDE WALL 400.8 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 011 |
(999) |
OTHER (ROOF)SPLICE BOX FOR A.C CONTROL WIRING NOT WORKING SPACE PROVIDED 110.26 |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 012 |
(999) |
OTHER (ROOF) ALUMINUM CONDUIT NOT SUPPORTED PROPERLY |
RSLV |
05/04/2017 |
05/04/2017 |
06/05/2017 |
| |
| 013 |
( 10) |
BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE (CELLAR) F/P CONDUCTORS UNDERSIZE AM. 695.6(C) |
RSLV |
07/20/2017 |
07/20/2017 |
08/14/2017 |
| |
| 014 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (CELLAR) EL. RM. : NO ACCESS TO LB 110.26 |
RSLV |
07/20/2017 |
07/20/2017 |
08/26/2017 |
| |
| 015 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (CELLAR) NO GEC IN F/P S. SW. 250.50,52 |
RSLV |
07/20/2017 |
07/20/2017 |
08/14/2017 |
| |
| 016 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (CELLAR) S. SW. FOR F/P UNDERSIZE AM. 695.4 B (1) |
RSLV |
07/20/2017 |
07/20/2017 |
08/14/2017 |
| |
| 017 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (CELLAR) NO NEUTRAL IN F/P S. SW. 215.4 B, 300.3 B, 20 |
RSLV |
07/20/2017 |
07/20/2017 |
08/14/2017 |
| |
| 018 |
(999) |
OTHER (CELLAR)F/P S. SW. LESS THAN 12" FROM PLP S. SW. AM. 695.4B3 |
RSLV |
08/14/2017 |
08/14/2017 |
08/26/2017 |