Premises: 225 GRAND STREET MANHATTAN BIN: 1090573     Block: 239   Lot: 15
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 227 GRAND ST Census Tract:   41 Health Area:  6800
CELLAR. 1/FL-7/FL, ROOF Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
Related Job Number:    121185859
DOB Cross Street(s):   ELIZABETH STREET,    BOWERY
Status:   C - JOB IS SIGNED OFF 09/28/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/17/2016 9:44 AM
Application Entered:   05/17/2016 Job Start Date:   05/17/2016
Last Change:   09/28/2017 Job End Date:   12/30/2016
Appointment Status:   
Last Inspection By:   WEISBART, F.       On     08/26/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $2,234.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121185859
Building Used As:   Z - Commercial/Residential (4  Stores, 23 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JIN ZHANG
Owner Business Name: 223 GRAND PROPERTY INC
Authorized Representative:  JIN ZHANG
Relationship To Owner:   PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  4  3-600A, 1-400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  24  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  6  2 SET 500MCM,4 SET 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  23  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    19  15    19  56         
001    14  14    14             
002    14               
003    36  80    30  36  20         
004    35  75    28  35  20         
005    35  75    28  35  20         
006    35  75    28  35  20         
007    31  50    23  31  12         
ROF                 
Buildings Total 222  401    154  222     148           
Total Units : 1147 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 23 #4-Wire 4 #10-Wire 1
Existing Meters 23 + New Meters 28 - Removed Meters 23 = Total Meters 28

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/17/2016 Notice: 1 - FIRST NOTICE 08/14/2017
Power Issued: 05/17/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M381720
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/04/2017 05/04/2017 BUR V (200) (12)
INSPECTION COMMENTS: FIRE PUMP NOT INSPECTED, LIMITED TIME FOR INSPECTION , MOTOR COUNT NEED TO BE AMENDED TO APPLICATION FOR EXHAUST FANS, A.C, PUMPS ETC
 
(2) 06/05/2017 06/06/2017 TOR J Y (30) (0)
INSPECTION COMMENTS: FAIL
 
(3) 07/20/2017 07/21/2017 EDB V R (55) (5)
INSPECTION COMMENTS: INSPECT CELLAR ONLY. SEE ATTACHMENT.
 
(4) 08/14/2017 08/14/2017 EDB V Y (75) (1)
INSPECTION COMMENTS: NO SPECIAL PERMISSION FOR INSTALLATION OF F/P S. SW. SEE ATTACHMENT.
 
(5) 08/26/2017 08/28/2017 FWE C R (15) (0)
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: M381720
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002)RECEPTACLE NOT GFCI PROTECTED NEAR HAIR WASHING SINK 210.8
RSLV 05/04/2017 05/04/2017 06/05/2017
 
002 (999) OTHER
(FLOOR: 008)APT 8B AND 5B RECEPTACLES NOT PLACED PROPERLY ON COUNTERTOP 210.52
RSLV 05/04/2017 05/04/2017 06/05/2017
 
003 (999) OTHER
(ALL FLOORS)ALL FLRS, EXIT LIGHT FIXTURE BOXES RECESS TOO FAR BACK IN WALL314.20
RSLV 05/04/2017 05/04/2017 06/05/2017
 
004 (999) OTHER
(CELLAR) EQUIPMENTS NOT LABEL PROPERLY 110.22
RSLV 05/04/2017 05/04/2017 06/05/2017
 
005 (999) OTHER
(CELLAR)PLP AND OTHER PANELS SHEET METAL SCREW USED TO SECURE GROUND BARS INPANELS 250.8
RSLV 05/04/2017 05/04/2017 06/05/2017
 
006 (999) OTHER
(CELLAR) FIRE ALARM CONDUIT NOT CONTINUOUS WITH ELECTRODE 250.64E
RSLV 05/04/2017 05/04/2017 06/05/2017
 
007 (999) OTHER
(CELLAR) ARC FLASH STICKERS NOT PROVIDED ON EQUIPMENTS 110.16
RSLV 05/04/2017 05/04/2017 06/05/2017
 
008 (999) OTHER
(CELLAR)FIRE PUMP DISCONNECT NOT 12 INCHES AWAY FROM SERVICE AMEN 695.4B3
RSLV 05/04/2017 05/04/2017 07/20/2017
 
009 (999) OTHER
(CELLAR)DISCONNECT FOR COMMERCIAL SPACES NOT BONDED PROPERLY FOR LOAD SIDECONDUIT 250.4
RSLV 05/04/2017 05/04/2017 06/05/2017
 
010 (999) OTHER
(CELLAR) SUMP PUMP FLEXIBLE CABLE RUNNING INSIDE WALL 400.8
RSLV 05/04/2017 05/04/2017 06/05/2017
 
011 (999) OTHER
(ROOF)SPLICE BOX FOR A.C CONTROL WIRING NOT WORKING SPACE PROVIDED 110.26
RSLV 05/04/2017 05/04/2017 06/05/2017
 
012 (999) OTHER
(ROOF) ALUMINUM CONDUIT NOT SUPPORTED PROPERLY
RSLV 05/04/2017 05/04/2017 06/05/2017
 
013 ( 10) BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE
(CELLAR) F/P CONDUCTORS UNDERSIZE AM. 695.6(C)
RSLV 07/20/2017 07/20/2017 08/14/2017
 
014 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(CELLAR) EL. RM. : NO ACCESS TO LB 110.26
RSLV 07/20/2017 07/20/2017 08/26/2017
 
015 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) NO GEC IN F/P S. SW. 250.50,52
RSLV 07/20/2017 07/20/2017 08/14/2017
 
016 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) S. SW. FOR F/P UNDERSIZE AM. 695.4 B (1)
RSLV 07/20/2017 07/20/2017 08/14/2017
 
017 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) NO NEUTRAL IN F/P S. SW. 215.4 B, 300.3 B, 20
RSLV 07/20/2017 07/20/2017 08/14/2017
 
018 (999) OTHER
(CELLAR)F/P S. SW. LESS THAN 12" FROM PLP S. SW. AM. 695.4B3
RSLV 08/14/2017 08/14/2017 08/26/2017