BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M381593
Premises: 107 UNIVERSITY PLACE MANHATTAN BIN: 1009196     Block: 564   Lot: 4
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 107 UNIVERSITY PL Census Tract:   61 Health Area:  5700
ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):   EAST 12 STREET,    EAST 13 STREET
Status:   C - JOB IS SIGNED OFF 03/30/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/13/2016 11:11 AM
Application Entered:   05/13/2016 Job Start Date:   09/06/2016
Last Change:   03/30/2017 Job End Date:   12/06/2017
Appointment Status:   
Last Inspection By:   ADMINISTRATION       On     03/21/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011970 Licensee Name: GUY A FORD
Firm: 004012 Firm Name: ALLIANCE ELEVATOR COMPANY
Firm Phone: 347-592-1555  Firm Address: 36-36 33RD STREET, SUITE 104 LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $180.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL LEHMAN
Owner Business Name: 107 UNIVERSITY ASS.
Authorized Representative:  SAME SAME
Relationship To Owner:   BUILDING MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1- 10 CIRCUIT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF            10         
Buildings Total            10           
Total Units : 11 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/03/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MODERNIZATION OF 1 ELEVATOR. NYC DEVICE # 1P20652

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M381593
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/03/2017 01/03/2017 PHG V (30) (4)
INSPECTION COMMENTS: DID NOT INSPECT PANEL
 
(2) 03/21/2017 03/30/2017 ADM C R (35) (0)
INSPECTION COMMENTS: CORRECTIONS MADE TO PREVIOUS OBJECTIONS.

OBJECTION FOR APPLICATION #: M381593
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF) 14 WIRE ON 20 AMP CKT BREAKER 240.3
RSLV 01/03/2017 01/03/2017 03/21/2017
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) 14 WIRE USED FOR CAR LIGHTS 210.19
RSLV 01/03/2017 01/03/2017 03/21/2017
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ROOF) GROUND WIRE ON ISOLATED BLOCK IS MAIN DISCONNECT 250.4
RSLV 01/03/2017 01/03/2017 03/21/2017
 
004 (356) RACEWAY LACKS MECHANICAL CONTINUITY
(ROOF) CONDUIT ENTERING DISCONNECT KO TOO BIG PIPE 300.10
RSLV 01/03/2017 01/03/2017 03/21/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.