BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M381512
Premises: 1379 LEXINGTON AVENUE MANHATTAN BIN: 1048274     Block: 1519   Lot: 52
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1379 LEXINGTON AV Census Tract:   148.02 Health Area:  3600
BSMT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   EAST 90 STREET,    EAST 91 STREET
Status:   I - AWAITING INSPECTION REQUEST
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/11/2016 2:04 PM
Application Entered:   05/11/2016 Job Start Date:   05/13/2016
Last Change:   01/27/2017 Job End Date:   06/23/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     01/26/2017      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  

License #: 010759 Licensee Name: YOUNG S CHOE
Firm: 001995 Firm Name: Y.S ELECTRIC
Firm Phone: 347-247-4894  Firm Address: 129-09 26TH AVENUE, # 203 FLUSHING NY 11354 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $70.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   HAIR SALON
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KARLA PELOSI
Owner Business Name: HAIR SALON
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1X200
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/11/2016 Notice:  
Power Issued: 05/11/2016 Response:  

Follow-Up:
Contractor's Comments:  SERVICE EQUIPMENT.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M381512
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/26/2017 01/27/2017 MQY J (15) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW UP. GENERAL CONTRACTOR WAS THERE TO REPRESENT JOB BUT HE DID NOT KNOW SCOPE OF WORK OR WANT TO OPEN UP DEVICES OR EQUIPMENT. FULL INSPECTION NEEDED WITH ELECTRICIAN PRESENT




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order