Electrical Application Details for App #: M381107
Premises: 372 5 AVENUE MANHATTAN BIN: 1015898     Block: 837   Lot: 40
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 372 5 AV Census Tract:   84 Health Area:  5200
6L Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10018 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 02/23/2022
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/02/2016 11:38 AM
Application Entered:   05/02/2016 Job Start Date:   05/02/2016
Last Change:   02/23/2022 Job End Date:   05/01/2017
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     02/23/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011878 Licensee Name: EDGAR LEVENSTEIN
Firm: 003500 Firm Name: CONTACT PLUS ELEC'L CORP
Firm Phone: 718-254-0291  Firm Address: 2922 SHELL ROAD BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $62.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEVEN SKUTELSKY
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  100 AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  6L  14  16  10               
Buildings Total 14  16  10                  
Total Units : 41 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/03/2022
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M381107
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/09/2021 11/09/2021 ASK V (43) (9)
INSPECTION COMMENTS: FAIL INSPECTION INCOMPLETE. OBJECTION ISSUED. ATOI STEVEN FULL INSPECTION AT RETURN .
 
(2) 02/03/2022 02/03/2022 HBU V R (45) (2)
INSPECTION COMMENTS: FAIL. RE-INSPECTION COMPLETED. OBJECTIONS ISSUED. ATOI KAZIM.
 
(3) 02/23/2022 02/23/2022 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000005822
 
(4) 02/23/2022 02/23/2022 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000005823

OBJECTION FOR APPLICATION #: M381107
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 006)CABINET LIGHTS NO ACCESS TO THE TRANSFORMERS ART. 410.144
RSLV 11/09/2021 11/09/2021 02/03/2022
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 006) PANEL NOT TO MOUNTED OVER STEPS ART. 110.26, 240.24F
RSLV 11/09/2021 11/09/2021 02/03/2022
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 006) BOX SET BACK T-OUT ART. 314.20
RSLV 11/09/2021 11/09/2021 02/03/2022
 
004 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 006)BATHROOM MIRRORS EXPOSE WIRE ART. 320.40, 320.15, 300.15
RSLV 11/09/2021 11/09/2021 02/03/2022
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 006) PANEL DIRECTORY NEEDS UPDATES ART.408.4
RSLV 11/09/2021 11/09/2021 02/03/2022
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 006) BATHROOM GFCI NOT PROVIDED ART 210.8
RSLV 11/09/2021 11/09/2021 02/03/2022
 
007 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 006)AFCI NOT PROVIDED FOR ALL LISTED AREAS T-OUT ART. 210.12B
RSLV 11/09/2021 11/09/2021 02/03/2022
 
008 (999) OTHER
(FLOOR: 006)APP NOT MATCH INSTALLATION (CONTRACTOR NEEDS TO OPEN NEW APP )
RSLV 11/09/2021 11/09/2021 02/03/2022
 
009 (999) OTHER
(FLOOR: 006)AFFIDAVIT FOR ALL KITCHEN APPLIANCES ART. 250.122, 250.146, 320.40,320.15, 110.2
RSLV 11/09/2021 11/09/2021 02/03/2022
 
010 (999) OTHER
(FLOOR: 006)APT. 6L CONTRACTOR NEEDS AFFIDAVIT FOR ALL KITCHEN APPLIANCES ART.250.122,250.146,320.40,320.15 AND 110.2.
RSLV 02/03/2022 02/03/2022 02/23/2022
 
011 (999) OTHER
(FLOOR: 006)APT. 6L PAA REQUIRED, CONTRACTOR NEEDS TO ADD 23 FIXTURES FOR ATOTAL OF 37,ADD 8 RECEPTACLES FOR A TOTAL OF 24 AND ADD 7 SWITCHESFOR A TOTAL OF 17.
RSLV 02/03/2022 02/03/2022 02/23/2022