BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M380673
Premises: 36 WEST 36 STREET MANHATTAN BIN: 1015906     Block: 837   Lot: 66
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 36 W36 ST Census Tract:   84 Health Area:  5200
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10018 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 11/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/20/2016 9:31 PM
Application Entered:   04/20/2016 Job Start Date:   04/20/2016
Last Change:   11/14/2017 Job End Date:   03/20/2017
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     07/24/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010910 Licensee Name: DAVID HARARI
Firm: 004667 Firm Name: SEGA ELECTRIC LLC
Firm Phone: 347-512-7985  Firm Address: 72-40 MAIN STREET FLUSHING NY 11367 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $544.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 36 WEST 36 ST ASSO.LLC
Authorized Representative:  YUDA ATON
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  100AMPS
B. 101 Up to 200 AMPS  1  200 AMPS
C. 201 Up to 600 AMPS  2  1PANEL+MAIN400A,1S.S400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  #2WIRE
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0WIRE
D. Over 250 MCM  2  SET 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 4 #10-Wire 2
Existing Meters 3 + New Meters 6 - Removed Meters 0 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/20/2016 Notice: 1 - FIRST NOTICE 06/28/2017
Power Issued: 04/20/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REQUEST 1 COPPER DETAIL CON ED BOX 1200 AMPS,1 400A FOR 1FL,1 PLP 200A,3METERS 100A FOR 2-3-4 FLOORS 100AMPS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M380673
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/27/2017 06/28/2017 TOR V (30) (6)
INSPECTION COMMENTS: FAIL CONTRACTOR NEED AMMEND APP TO CORRECT NR OF SERVICE SW AND PANELS AND SUB FEEDERS
 
(2) 07/24/2017 07/24/2017 MLF C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M380673
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) END LINE BOX TO SERVICE SW
RSLV 06/27/2017 06/27/2017 07/24/2017
 
002 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(BASEMENT) SUB FEEDER FOR 3 RD FL OVERFUSED
RSLV 06/27/2017 06/27/2017 07/24/2017
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) LL NOT COVER ABOVE SERVICE
RSLV 06/27/2017 06/27/2017 07/24/2017
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT) T-OUT
RSLV 06/27/2017 06/27/2017 07/24/2017
 
005 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) T-OUT
RSLV 06/27/2017 06/27/2017 07/24/2017
 
006 (999) OTHER
(BASEMENT) ARC FLASH LABELS NOT PROVIDED 110.16
RSLV 06/27/2017 06/27/2017 07/24/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order