Electrical Application Details for App #: M380640
Premises: 626 5 AVENUE MANHATTAN BIN: 1083860     Block: 1266   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 630 5TH AV Census Tract:   104 Health Area:  4800
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10020 Community Board:   105
Special Place Name:   TISHMAN SPEYER
DOB Cross Street(s):   EAST 50 STREET,    EAST 51 STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 12/15/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/20/2016 10:22 AM
Application Entered:   04/20/2016 Job Start Date:   04/20/2016
Last Change:   12/15/2017 Job End Date:   06/30/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     12/15/2017      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 011456 Licensee Name: RALPH OCCHIPINTI
Firm: 000064 Firm Name: ADCO ELEC'L CORP
Firm Phone: 718-494-4400  Firm Address: 201 EDWARD CURRY AVENUE STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $745.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANTHONY LAMORTE
Owner Business Name: RCPI LANDMARK PROPERTIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  11  4#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  7  5- 4#3/0, 2- 4#4/0
D. Over 250 MCM  3  4#500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 12/15/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  JM JOB #160063 DEMO - REMOVE AND RELOCATE EXISTING SWITCHGEAR WITHIN SAME ROOM TO ALLOW FOR WALL REMOVAL. NO CON ED SHUTDOWN REQUIRED OR CHANGE TO EXISTING SERVICE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M380640
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/16/2016 06/17/2016 PHG V (55) (3)
INSPECTION COMMENTS: PICKED UP LOADS 1000 AMPS FROM 2 FUSE ADDRESS IS 636 5 AVE
 
(2) 08/24/2016 08/29/2016 EDB V R (55) (1)
INSPECTION COMMENTS: SEE ATTACHMENT. CONTRACTOR RELOCATE EXISTING DB , NO NEW EQUIPMENT , JOB DONE FROM 2ND FUSE.
 
(3) 12/15/2017 12/15/2017 EDB J X (45) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT READY FOR INSPECTION. SEE ATTACHMENT.

OBJECTION FOR APPLICATION #: M380640
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) 225 AMP ON 3/0 WIRE FOR ELEVATOR DP EL CSI 240.3
RSLV 06/16/2016 06/16/2016 08/24/2016
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) 3 200 AMP BUCKETS IN DP HVAC CS OVER FUSED 240.3
RSLV 06/16/2016 06/16/2016 08/24/2016
 
003 (999) OTHER
(BASEMENT) NO FUSE COORDINATION FOR 1000 AMP LOAD 240.12
RSLV 06/16/2016 06/16/2016 08/24/2016
 
004 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(CELLAR) TEMP. WIRING NOT REMOVED
OPEN 08/24/2016 08/24/2016