BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M380555
Premises: 124 LUDLOW STREET MANHATTAN BIN: 1005328     Block: 410   Lot: 44
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 124 LUDLOW ST Census Tract:   18 Health Area:  7400
1FL Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   DELANCEY STREET,    RIVINGTON STREET
Status:   C - JOB IS SIGNED OFF 12/02/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/18/2016 3:53 PM
Application Entered:   04/18/2016 Job Start Date:   04/19/2016
Last Change:   12/02/2016 Job End Date:   04/19/2017
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     12/01/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  

License #: 011793 Licensee Name: JEONG YUNG
Firm: 003404 Firm Name: INTELOGIC ELECTRIC, INC.
Firm Phone: 718-768-3188  Firm Address: 254 40TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $66.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   OTHER
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TONY FOK
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    12  18    10  12         
Buildings Total 12  18    10  12              
Total Units : 57 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING FOR OUTLETS, LIGHTS, SWITCHES AND HVAC. INSTALL NEW 3 PHASE SUB-PANEL.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M380555
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/01/2016 12/02/2016 TOR C (30) (0) Y
INSPECTION COMMENTS: NONE




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order