Electrical Application Details for App #: M380169
Premises: 139 LUDLOW STREET MANHATTAN BIN: 1005359     Block: 411   Lot: 29
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 139 LUDLOW ST Census Tract:   30.01 Health Area:  6600
BASE- ROOF Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   RIVINGTON STREET,    STANTON STREET
Status:   C - JOB IS SIGNED OFF 12/02/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/07/2016 9:00 PM
Application Entered:   04/07/2016 Job Start Date:   04/07/2016
Last Change:   12/02/2016 Job End Date:   06/01/2016
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     12/01/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010698 Licensee Name: ERNEST JOCHEN
Firm: 001918 Firm Name: BIG SHOT ELECTRIC CORP.
Firm Phone: 718-292-0033  Firm Address: 710 EAST 135TH STREET BRONX NY 10454 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $595.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CLUB
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 139 LUDLOW ACQUISTIONS LL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    110  95    26  110  20  45     
001    145  140    27  145  13  18     
002    90  122    25  90  20  12  30     
003    136  150    35  136  10  10     
004    88  103    16  103     
ROF    24  10    24  24  130     
Buildings Total 593  620    133  608     228     51      
Total Units : 2233 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/04/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M380169
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/02/2016 08/04/2016 PHG V (125) (10)
INSPECTION COMMENTS: FULL INSPECT DONE. BREAKER ON ROOF PENDING TRIP OF 500 AMP WITH 600 AMP FRAME FEEDING CHILLER
 
(2) 11/18/2016 11/18/2016 DNM J Y (39) (0)
INSPECTION COMMENTS: (1) OBJECTION REMAINS OPEN.
 
(3) 12/01/2016 12/02/2016 TOR C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS ONLY

OBJECTION FOR APPLICATION #: M380169
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 001) FRONT DESK LIGHTS NO GRND 250.122
RSLV 08/02/2016 08/02/2016 11/18/2016
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 001) NO GFCI IN MENS RM LIGHTS WITH OUTLETS 210.8
RSLV 08/02/2016 08/02/2016 11/18/2016
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 002) 2 WIRE ON 125 AMP BREAKER KITCHEN PANEL 240.3
RSLV 08/02/2016 08/02/2016 11/18/2016
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 002) GFCI MISSING IN COMMERCIAL KITCHEN 210.8
RSLV 08/02/2016 08/02/2016 11/18/2016
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)LIGHTS IN STAIR CASE AND OUTSIDE MENS RM NO GRND 250.122
RSLV 08/02/2016 08/02/2016 11/18/2016
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS)ALL OUTSIDE EM LIGHTS NOT LISTED FOR WET LOCATION 410.10
RSLV 08/02/2016 08/02/2016 11/18/2016
 
007 (999) OTHER
(ALL FLOORS) NO WIRE SUPPOTR FOR 800 AMP LINE TO ROOF 300.19
RSLV 08/02/2016 08/02/2016 11/18/2016
 
008 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT) UNDER SIZE EQUIPMENT GRND FEEDIND COMPRESSORS 250.122
RSLV 08/02/2016 08/02/2016 12/01/2016
 
009 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(BASEMENT) COMPRESSORS FED WITH PLASTIC SEAL TIGHT 356.10 AMD
RSLV 08/02/2016 08/02/2016 11/18/2016
 
010 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ROOF) 2 300MCM WIRES UNDER 1 LUG FOR CHILLER
RSLV 08/02/2016 08/02/2016 11/18/2016