| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 001) FRONT DESK LIGHTS NO GRND 250.122 |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |
| |
| 002 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 001) NO GFCI IN MENS RM LIGHTS WITH OUTLETS 210.8 |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |
| |
| 003 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (FLOOR: 002) 2 WIRE ON 125 AMP BREAKER KITCHEN PANEL 240.3 |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 002) GFCI MISSING IN COMMERCIAL KITCHEN 210.8 |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS)LIGHTS IN STAIR CASE AND OUTSIDE MENS RM NO GRND 250.122 |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |
| |
| 006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ALL FLOORS)ALL OUTSIDE EM LIGHTS NOT LISTED FOR WET LOCATION 410.10 |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) NO WIRE SUPPOTR FOR 800 AMP LINE TO ROOF 300.19 |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |
| |
| 008 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) UNDER SIZE EQUIPMENT GRND FEEDIND COMPRESSORS 250.122 |
RSLV |
08/02/2016 |
08/02/2016 |
12/01/2016 |
| |
| 009 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (BASEMENT) COMPRESSORS FED WITH PLASTIC SEAL TIGHT 356.10 AMD |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |
| |
| 010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ROOF) 2 300MCM WIRES UNDER 1 LUG FOR CHILLER |
RSLV |
08/02/2016 |
08/02/2016 |
11/18/2016 |