| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 001) IMPROPER KITCHEN ISLAND PLACEMENT 210.52 |
RSLV |
03/01/2017 |
03/01/2017 |
06/06/2017 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS) FRONT DOOR AND SERVICE RM |
RSLV |
03/01/2017 |
03/01/2017 |
06/06/2017 |
| |
| 003 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS) MISSING AFCI PROTECTION T OUT 210.12 |
RSLV |
03/01/2017 |
03/01/2017 |
06/06/2017 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS) EXPOZSED BULB IN CLOTHES CLOSET 410.16 |
RSLV |
03/01/2017 |
03/01/2017 |
06/19/2017 |
| |
| 005 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) NO BOND IN TROUGH 250.92 |
RSLV |
03/01/2017 |
03/01/2017 |
06/06/2017 |
| |
| 006 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (BASEMENT) IMPROPER PLACEMENT OF WATER GROUND 250.24 |
RSLV |
03/01/2017 |
03/01/2017 |
06/19/2017 |
| |
| 007 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (BASEMENT) NO BONDING JUMPER PROVIDED SERVICE SW |
RSLV |
03/01/2017 |
03/01/2017 |
06/19/2017 |
| |
| 008 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (OPEN SPACE) NO OUTLET IN FRONT OF HOUSE 210.52 |
RSLV |
03/01/2017 |
03/01/2017 |
06/06/2017 |
| |
| 009 |
(111) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (ROOF) NO WORKING SPACE FOR AC WORK 110.26 |
RSLV |
03/01/2017 |
03/01/2017 |
06/06/2017 |
| |
| 010 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ROOF) ALL OUTDOOR SW NOT GROUNDED 250.8 |
RSLV |
03/01/2017 |
03/01/2017 |
06/06/2017 |
| |
| 011 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER (FLOOR: 002)BATHROOM : OPEN LIGHT FIXTURE IN WET/ DAMP LOCATION 410.10 |
RSLV |
06/06/2017 |
06/06/2017 |
06/19/2017 |
| |
| 012 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ALL FLOORS)PANELS : ZIP SCREW USED FOR GND BUS BAR 250.8 A 5 |
RSLV |
06/06/2017 |
06/06/2017 |
06/19/2017 |
| |
| 013 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (ALL FLOORS)FRENCH BALCONY MISSING RECEPTACLE AM. 210.52 E 3 |
RSLV |
06/06/2017 |
06/06/2017 |
06/19/2017 |
| |
| 014 |
(340) |
RECEPTACLES NOT TAMPERPROOF (ROOF) CLOCK RECEPTACLE NOT TR 406.11 |
RSLV |
06/06/2017 |
06/06/2017 |
06/19/2017 |