BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M379952
Premises: 233 WEST 42 STREET MANHATTAN BIN: 1087142     Block: 1014   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 247 W 42ND Census Tract:   119 Health Area:  5200
2ND FL Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10036 Community Board:   105
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/03/2016 11:49 PM
Application Entered:   04/03/2016 Job Start Date:   04/03/2016
Last Change:   08/22/2025 Job End Date:   04/03/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     08/23/2016      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 011940 Licensee Name: RODNEY SCOTT
Firm: 003580 Firm Name: SCOTT ELEC'L SERVICE, LLC
Firm Phone: 718-234-1602  Firm Address: 40 MACON STREET BROOKLYN NY 11216 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $148.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   J - Theatre
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: DTA LEASEHOLD OWNER LLC
Authorized Representative:  RODNEY SCOTT
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002      42                 
Buildings Total   42                    
Total Units : 43 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 08/24/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M379952
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/23/2016 05/24/2016 STP V (35) (6)
INSPECTION COMMENTS: FAIL NEED TO FILE TRANSFORMER. DID NOT INSPECT BRANCH CIRCUITS IN FIELD.
 
(2) 07/12/2016 07/12/2016 CBK V Y (44) (3)
INSPECTION COMMENTS: DID NOT INSPECT THEATRE ROOM.
 
(3) 08/23/2016 08/24/2016 TUR J X (50) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR 5 TIMES LEFT MESSAGES NO ANSWER NO RETURN CALL WAITED WITH MANAGER OF THEATRE AND HE CALLED GC AND THEY COULD NOT REACH ELECTRICIAN, MOVIE IN THEATRE COULD NOT DO VISUAL AT TIME.

OBJECTION FOR APPLICATION #: M379952
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 003) NO METALIC CONTINUITY OF RACEWAY TO PANEL 300.12
OPEN 05/23/2016 05/23/2016
 
002 (999) OTHER
(FLOOR: 003) WIRES NOT DERARTED 310.15
RSLV 05/23/2016 05/23/2016 07/12/2016
 
003 (999) OTHER
(FLOOR: 003) GROUND TO STEAL UNDERSIZED 250.66
RSLV 05/23/2016 05/23/2016 07/12/2016
 
004 (999) OTHER
(FLOOR: 003) EMT CHANGEOVER USED TO MAKE GROUND CONTINOUS XFR 110.3
RSLV 05/23/2016 05/23/2016 07/12/2016
 
005 (999) OTHER
(FLOOR: 003) NO HIGH VOLT STICKERS ON PANELS 408.60 AMND
RSLV 05/23/2016 05/23/2016 07/12/2016
 
006 (999) OTHER
(FLOOR: 003) LOW VOLT COLORS USED AS HIGH VOLT 277 210.5
OPEN 05/23/2016 05/23/2016
 
007 (271) BONDING INSUFFICIENT, OVER 250 VOLTS
(FLOOR: 002) BANDING BUSHING NEEDED IN HI VOLTAGE PANEL.
OPEN 07/12/2016 07/12/2016
 
008 (999) OTHER
(FLOOR: 002) GROUPING IN PANELS
OPEN 07/12/2016 07/12/2016
 
009 (999) OTHER
(FLOOR: 002) BREAKER TIES NEEDED IN PANELS. 210.4
OPEN 07/12/2016 07/12/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.