BIS Menu  |  Bldg Info Search  |  Plumb. Inspections  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M379863
Premises: 16 WEST 12 STREET MANHATTAN BIN: 1009581     Block: 575   Lot: 44
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 16 W 12 ST Census Tract:   63 Health Area:  5700
CELLAR, BSMT, FL 1-4,ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 07/03/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/31/2016 12:04 PM
Application Entered:   03/31/2016 Job Start Date:   04/01/2016
Last Change:   07/03/2018 Job End Date:   04/01/2017
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     07/03/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $1,517.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 16 WEST 12 HOLDINGS LLC
Authorized Representative:  KANE KESSLER
Relationship To Owner:   PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  1 X 400AMP, 1 X 600AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  13  42 CIRCUITS, 225 AMP
D. 3 Phase Over 225 AMPS  1  6 POLE 600 AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    50  30  10  50  10     
BAS    50  30  10  12  50     
001    85  36  11  10  85     
002    85  38  12  12  85     
003    85  35  12  12  85     
004    86  41  15  86     
ROF    23    23  11  40     
Buildings Total 464  218  69  69  464     51     43      
Total Units : 1378 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/20/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M379863
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/06/2018 06/06/2018 CBK V (225) (6)
INSPECTION COMMENTS: I DID NOT INSPECT ELEVATOR, CONTRACTOR SAID HE DID NOT DO ELEVATOR.
 
(2) 06/20/2018 06/20/2018 DWB V R (45) (2)
INSPECTION COMMENTS: OBJECTION ISSUED,
 
(3) 07/03/2018 07/03/2018 CLC C R (19) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: M379863
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (146) APPLIANCE DISCONNECT NOT PROPERLY LOCATED/LOCKABLE
(FLOOR: 002) TOWEL WARMER NEED LOCKABLE DISCONNECT.
RSLV 06/06/2018 06/06/2018 06/20/2018
 
002 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(BASEMENT) FIRE PUMP SERVICE SWITCH NOT PROPERLY LABELED.
RSLV 06/06/2018 06/06/2018 06/20/2018
 
003 (146) APPLIANCE DISCONNECT NOT PROPERLY LOCATED/LOCKABLE
(BASEMENT) DISCONNECT NEEDED FOR SAUNA.
RSLV 06/06/2018 06/06/2018 06/20/2018
 
004 (218) UNAPPROVED FIXTURES INSTALLED IN ALL CLOTHES CLOSETS
(BASEMENT) FEEDER FOR LUTRON PANELS IN SAME TROUGH WITH CAT5.
RSLV 06/06/2018 06/06/2018 06/20/2018
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) FIRE PUMP SERVICE SWITCH NOT GROUNDED AND BONDED.
RSLV 06/06/2018 06/06/2018 06/20/2018
 
006 (999) OTHER
(BASEMENT) FIRE PUMP OVER-FUSED. AM. 695.4
RSLV 06/06/2018 06/06/2018 06/20/2018
 
007 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(BASEMENT)250.4(A)(4), CONTRACTOR TO INSTALL MIGB IN ELEVATOR DISCONNECT.
RSLV 06/20/2018 06/20/2018 07/03/2018
 
008 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) 240.3, ELEVATOR DISCONNECT ARE OVER FUSE
RSLV 06/20/2018 06/20/2018 07/03/2018