BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M379856
Premises: 323 HUDSON STREET MANHATTAN BIN: 1010375     Block: 597   Lot: 62
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 325 HUDSON ST Census Tract:   37
ROOF Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   HUDSON STREET,    GREENWICH STREET
Status:   C - JOB IS SIGNED OFF 04/06/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   03/31/2016 Job Start Date:   03/21/2016
Last Change:   04/06/2017 Job End Date:   06/25/2016
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     04/06/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011436 Licensee Name: NICHOLAS J STEFANOU
Firm: 002938 Firm Name: NJS ELEC'L SERVICES CORP.
Firm Phone: 718-784-9111  Firm Address: 36-16 13TH STREET L.I.C. NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $565.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53453     Submittal #: 15A0705  
Owner / Occup: ANTHONY LINDQUIST
Owner Business Name: LINCOLN PROPERTY CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  2-3#600MCM,4-4#500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  3000 AMP BOARD
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/16/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M379856
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/16/2017 02/16/2017 TOR V (120) (3)
INSPECTION COMMENTS: FAIL
 
(2) 04/06/2017 04/06/2017 MQY C R (95) (0)
INSPECTION COMMENTS: 2 GENERATORS FEEDS A 3POLE ATS ON THE ROOF, THE ATS FEEDS A NEW SWITCH GEAR ON THE ROOF. THE LOAD OF THE NEW SWITCH GEAR IS (3) 4-POLE ATS LOCATED ON THE 8TH 9TH AND 4TH FLOOR. NEUTRAL IS BONDED IN THE 1ST DISCONNECT AFTER THE GENERATOR.

OBJECTION FOR APPLICATION #: M379856
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(ROOF) NAT AS PER ADVISORY ( THIS IS 4 WIRE SYSTEM)
RSLV 02/16/2017 02/16/2017 04/06/2017
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) GROUND NOT SUFFICIENT
RSLV 02/16/2017 02/16/2017 04/06/2017
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ROOF) ATS ON THE ROOF NOT DESIGN FOR 4 W SYSTEM.
RSLV 02/16/2017 02/16/2017 04/06/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order