| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
3PHASE 225AMPS |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS (FLOOR: 005) WINDOW UNITS |
RSLV |
03/23/2018 |
03/23/2018 |
05/31/2018 |
| |
| 002 |
(999) |
OTHER (FLOOR: 005)ALL OUTLETS FOR WINDOW A/C UNITS NOT AFCI PROTECTED ART. 210.12 |
RSLV |
03/23/2018 |
03/23/2018 |
05/31/2018 |
| |
| 003 |
(999) |
OTHER (FLOOR: 005)SURFACE MOUNT INCANDESCENT CLOSET LIGHT WITH IN 12" FROM STORAGEART. 410.16 |
RSLV |
03/23/2018 |
03/23/2018 |
05/31/2018 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)BOX SET BACK IN COMBUSTIBLE MATERIAL (ALL OUTLETS IN WOOD BASEBOARD) ART. 314.20 |
RSLV |
03/23/2018 |
03/23/2018 |
05/31/2018 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 004) NO GROUND IN FMC MAIN FEEDER 250.122 |
RSLV |
05/31/2018 |
05/31/2018 |
10/11/2018 |
| |
| 006 |
(999) |
OTHER (FLOOR: 004) PULL BOX GLUED SHUT IN CLOSET 314.29 |
RSLV |
05/31/2018 |
05/31/2018 |
10/11/2018 |
| |
| 007 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 005) MAN MASTER CLOSET HANGING LOGHT NOT GROUNDED 250.122 |
RSLV |
05/31/2018 |
05/31/2018 |
10/11/2018 |
| |
| 008 |
(999) |
OTHER (FLOOR: 005) PENDANT FIXTURE IN BATH RM TOO CLOSE TO TUB 410.10 |
RSLV |
05/31/2018 |
05/31/2018 |
10/11/2018 |
| |
| 009 |
(340) |
RECEPTACLES NOT TAMPERPROOF (ALL FLOORS) AC NOT TAMPER 406.11 |
RSLV |
05/31/2018 |
05/31/2018 |
10/11/2018 |
| |
| 010 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS) AFCI NOT PROVIDED IN N NEEDED AREAS 210.12 |
RSLV |
05/31/2018 |
05/31/2018 |
10/11/2018 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS) EXPOSED BULB IN BOTH CLOTHES CLOSET 410.16 |
RSLV |
05/31/2018 |
05/31/2018 |
10/11/2018 |
| |
| 012 |
(999) |
OTHER (ALL FLOORS) LOAD CALUATION NEEDED FROM 175 AMP FEED FOR DUPLEX APT |
RSLV |
05/31/2018 |
05/31/2018 |
08/14/2018 |
| |
| 013 |
(999) |
OTHER (FLOOR: 004) 250.66, GROUND CONDUCTOR NOT PROPER SIZE, FOR 200 AMP. |
RSLV |
07/30/2018 |
07/30/2018 |
10/11/2018 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS)314.20, BOXES SET BACK WITH COMBUSTIBLE MATERIAL, WALL PAPER. |
RSLV |
07/30/2018 |
07/30/2018 |
10/11/2018 |