BIS Menu  |  DOB Violations  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M379670
Premises: 14 EAST 53 STREET MANHATTAN BIN: 1088582     Block: 1288   Lot: 56
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 510 MADISON AV Census Tract:   102 Health Area:  4800
BASEMENT/FIRST/MEZZ Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):   EAST 52 STREET,    EAST 53 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/28/2016 11:04 AM
Application Entered:   03/28/2016 Job Start Date:   03/29/2016
Last Change:   08/22/2025 Job End Date:   05/31/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ADMINISTRATION       On     02/23/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010275 Licensee Name: FRANK RAPPO
Firm: 001195 Firm Name: R & L SYSTEMS, INC.
Firm Phone: 718-397-5394  Firm Address: 37-20 56TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
T - TEMPORARY LIGHT & POWER
Total Fee:  $180.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CAROLE MOLESKY
Owner Business Name: CORCON
Authorized Representative:  CAROLE MOLESKY
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/O
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                75 
001                   
MEZ                   
Buildings Total 12                   75 
Total Units : 98 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 03/28/2016 Notice: 1 - FIRST NOTICE 02/28/2017
Power Issued: 03/28/2016 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M379670
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/23/2017 02/28/2017 ADM V (39) (1)
INSPECTION COMMENTS: GROUNDING CONDUCTOR NOT RUN FROM METER TO LOAD IN SUB CELLAR. DID NOT SEE OTHER END WHERE 350 MCM WAS RUN.

OBJECTION FOR APPLICATION #: M379670
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(CELLAR)GROUNDING CONDUCTOR PULLED OUT OF ONE CONDUIT. 300.3B 1 & 250.122
OPEN 02/23/2017 02/23/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  DOB Violations  |  Electrical Inspection Work Order  |  Back