| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
200 AMP |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
30 CKTS |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (GROUND FLOOR)THROUGHOUT. WIRING METHOD USED TO WIRE ALL LIGHTING FIXTURES NOTAPPROVED. ZIP CORD USED. NEC 400 |
OPEN |
01/06/2017 |
01/06/2017 |
|
| |
| 002 |
(999) |
OTHER (GROUND FLOOR)MATERIAL USED NOT SUITABLE FOR PURPOSE INTENDED . EMT CONNECTORUSED IN LIEU OF BX CONNECTOR. SEE PANEL BOTTOM, BOX ABOVE IRONINGDESK ,BACK ROOM. AMEND 110.2 |
OPEN |
01/06/2017 |
01/06/2017 |
|
| |
| 003 |
(999) |
OTHER (GROUND FLOOR) RECEPTACLES NOT GROUNDED PROPERLY. NEC 250.146 |
OPEN |
01/06/2017 |
01/06/2017 |
|
| |
| 004 |
(999) |
OTHER (GROUND FLOOR)BACK ROOM . CEILING OUTLETS HAVE NOT BEEN CLOSED. NEC 314 |
OPEN |
01/06/2017 |
01/06/2017 |
|
| |
| 005 |
(999) |
OTHER (GROUND FLOOR)NO SUFFICIENT WORKING CLEARANCE AND ACCESS PROVIDED FOR OUTDOOR A/CDISCONNECT SWITCH. NEC 110.26 |
OPEN |
01/06/2017 |
01/06/2017 |
|
| |
| 006 |
(999) |
OTHER (GROUND FLOOR)NO RECEPTACLE PROVIDED WITHIN 25 FT OF OUTDOOR A/C UNIT. NEC 210 |
OPEN |
01/06/2017 |
01/06/2017 |
|
| |
| 007 |
(999) |
OTHER (GROUND FLOOR)SERVICE SWITCH WHERE TAP WAS MADE FROM NOT GROUNDED. NEC 250.24 |
OPEN |
01/06/2017 |
01/06/2017 |
|