Electrical Application Details for App #: M379451
Premises: 304 EAST 64 STREET MANHATTAN BIN: 1044387     Block: 1438   Lot: 44
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 304 E 64TH ST Census Tract:   110 Health Area:  4900
2ND, 3RD & 4TH Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 07/07/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/22/2016 10:11 AM
Application Entered:   03/22/2016 Job Start Date:   03/24/2016
Last Change:   07/07/2016 Job End Date:   06/20/2016
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     05/27/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011349 Licensee Name: ROBERT LAPPETITO
Firm: 001401 Firm Name: T. DIRUSSO ELEC'L CONT IN
Firm Phone: 718-821-1646  Firm Address: 63-23 METROPOLITAN AVE. MIDDLE VILLAGE NY 11379 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
011007 DI RUSSO, ANTHONY 001401 T. DIRUSSO ELEC'L CONT IN RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $498.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   G - Garage
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: AVIS / BUDGET RENTAL
Authorized Representative:  ROBERT LAPPETITO
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  (6) - 100A AND (2) 225A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    27      27     
003    38      46  10  12  10     
004    29      29         
Buildings Total 94      10  102     22     14      
Total Units : 242 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/19/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M379451
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/18/2016 04/19/2016 STP V (110) (5)
INSPECTION COMMENTS: FAIL.
 
(2) 05/27/2016 05/31/2016 BMP C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M379451
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 003) PANEL RPL3-1, RP3L-3 GREEN WIRES ON NEUTRAL BAR 200.6
RSLV 04/18/2016 04/18/2016 05/27/2016
 
002 (999) OTHER
(FLOOR: 003) NO ARC FLASH STICKERS TOUT PANELS 110.16
RSLV 04/18/2016 04/18/2016 05/27/2016
 
003 (999) OTHER
(FLOOR: 004) SPLICE BOX BURIED FOR PANEL 314.29
RSLV 04/18/2016 04/18/2016 05/27/2016
 
004 (999) OTHER
(ALL FLOORS)AC USED WITH FLEX CORD IN CEILING TOUT ALL FLOORS 400.8
RSLV 04/18/2016 04/18/2016 05/27/2016
 
005 (999) OTHER
(ROOF) NO GFI FOR AC SERVICING ROOF 210..63
RSLV 04/18/2016 04/18/2016 05/27/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.