BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
Building Overview Work Items |
QUANTITY |
DESCRIPTION |
SERVICE SWITCHES |
|
A. Up to 100 AMPS |
0 |
|
B. 101 Up to 200 AMPS |
0 |
|
C. 201 Up to 600 AMPS |
0 |
|
D. 601 Up to 1200 AMPS |
0 |
|
E. Over 1200 AMPS |
0 |
|
SER. ENT. & FDR COND (EACH SET) |
|
A. Up to #2 CONDUCTOR |
3 |
(3) #2 |
B. Over #2 to 1/0 |
0 |
|
C. Over 1/0 to 250 MCM |
1 |
3? |
D. Over 250 MCM |
0 |
|
PANELS |
|
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
C. 3 Phase Up to 225 AMPS |
3 |
(1)277/480; (2)102/208 |
D. 3 Phase Over 225 AMPS |
0 |
|
ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
B. Each Additional 10 Floors Or Less |
0 |
|
BOILER CONTROLS |
0 |
|
OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
|
001 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 040) JUNCTION BOXES ARE OPEN IN ELECTRIC CLOSETS. |
OPEN |
12/19/2016 |
12/19/2016 |
|
|
002 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 040) OPEN KOS IN PANELS. |
OPEN |
12/19/2016 |
12/19/2016 |
|
|
003 |
(999) |
OTHER (FLOOR: 040) BREAKER TIE NEEDED IN HI VOLTAGE PANEL. 210.4 |
OPEN |
12/19/2016 |
12/19/2016 |
|
|
004 |
(999) |
OTHER (FLOOR: 040) TRANSFORMER SEC. DOUBLE TAPPED. 240.21 |
OPEN |
12/19/2016 |
12/19/2016 |
|
|
005 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 040) GEC FROM XFRMR TO KNEE 250.30 110.3 |
OPEN |
01/06/2017 |
01/06/2017 |
|
|
006 |
(999) |
OTHER (FLOOR: 040) GEC UNDERSIZED TO STEEL XFRMR 250.6 |
OPEN |
01/06/2017 |
01/06/2017 |
|
|
007 |
(999) |
OTHER (FLOOR: 040) SECONDARY XFRMR WIRE 3/0 UNDERSIZED KVA XFRMR 240.4 |
OPEN |
01/06/2017 |
01/06/2017 |
|