| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
49 |
|
| B. 101 Up to 200 AMPS |
2 |
|
| C. 201 Up to 600 AMPS |
2 |
|
| D. 601 Up to 1200 AMPS |
1 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
49 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
|
| D. Over 250 MCM |
4 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
49 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
3 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS) BOXES NOT SECURED, ALL UNIT A/C RECEPTACLES ART. 314.23 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) ALL UNITS ALL A/C RECEPTACLES NOT GROUNDED ART. 250.146 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 003 |
(999) |
OTHER (BASEMENT)PANIC BARS NOT PROVIDED ON THE ELECTRICAL SERVICE ROOM DOORS ART.110.25 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 004 |
(999) |
OTHER (BASEMENT) FIRE PUMP SERVICE SWITCH FUSE OVERSIZED AM. 694.5 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 005 |
(999) |
OTHER (BASEMENT) SERVICE SWITCHES NOT IDENTIFIED AM. 230.72 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 006 |
(999) |
OTHER (BASEMENT) ARCH FLUSH WARNING LABELS NOT PROVIDED T-OUT ART. 110.16 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 007 |
(999) |
OTHER (BASEMENT) WATER DAMAGE IN THE END BOX ART. 110.3 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 008 |
(999) |
OTHER (BASEMENT) NEUTRAL NOT PROVIDED IN THE FIRE PUMP SERVICE SWITCH |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 009 |
(999) |
OTHER (BASEMENT)FIRE ALARM SERVICE SWITCH CONDUCTORS UNDERSIZED AM. 230.31 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 010 |
(999) |
OTHER (BASEMENT)PARALLEL SETS OF CONDUCTORS NOT THE SAME, 800 AMP SERVICE SWITCHART. 310.4 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 011 |
(999) |
OTHER (BASEMENT)NEUTRAL BONDED BEYOND SERVICE, FIRE ALARM DISCONNECT NEXT TO ATSART. 250.24 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 012 |
(999) |
OTHER (ROOF) FIRE ALARM NOT PROPERLY FEED ON GENERATOR SIDE ART. 760.41 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 013 |
(999) |
OTHER (ROOF) FIRE PUMP NOT PROPERLY FEED ON GENERATOR SIDE AM. 695.4 |
RSLV |
06/07/2019 |
06/07/2019 |
10/08/2019 |
| |
| 014 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL (ALL FLOORS)ENTIRE APPLICATION NEEDS TO BE RIFLED CORRECTLY, AND REFILED FORADVISORY IF NECESSARY SEE SERVICE SWITCH COUNT INSPECTORS DO NOTCERTIFY |
RSLV |
09/27/2019 |
09/27/2019 |
10/08/2019 |
| |
| 015 |
(999) |
OTHER (ALL FLOORS) THIS APPLICATION IS NOT FILED CORRECTLY CONTRACTOR NEEDS TO REFILE ENTIRE APP CHECK FOR ADVISORY IF INSTALL IS OVER 1000KVA ALSO REMOVE THE ELEVATORS FROM THE APP , ALL SWITCHES THAT ARE FORTHE ELEVATOR AND CAR LIGHTS TO BE FILED IN FLOOR DESCRIPTION, AND ALL SWITCHES NOT SERVICE SWITCHES NEED TO BE ADDED ON THE LOORS THEY A |
RSLV |
10/02/2019 |
10/02/2019 |
10/08/2019 |