BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M379026
Premises: 59 WEST 12 STREET MANHATTAN BIN: 1066992     Block: 576   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 59 W 12 ST Census Tract:   63 Health Area:  5700
6G Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 02/13/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/11/2016 9:32 AM
Application Entered:   03/11/2016 Job Start Date:   03/21/2016
Last Change:   02/13/2017 Job End Date:   03/21/2017
Appointment Status:   
Last Inspection By:   WEISBART, F.       On     02/11/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011983 Licensee Name: PETER Z LI
Firm: 003654 Firm Name: P.L. ELEC'L CONTR'G CORP
Firm Phone: 212-608-8868  Firm Address: 25 MONROE STREET.1ST FLOOR NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $60.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JENNIFER JOHNSO BLALOCK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  6G  15             
Buildings Total 15                
Total Units : 32 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/12/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M379026
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/10/2016 12/12/2016 GYM V (45) (3)
INSPECTION COMMENTS: NEW OBJECTION.
 
(2) 02/11/2017 02/13/2017 FWE C R (15) (0)
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: M379026
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 006) GREEN WIRES USED PHASE.
RSLV 12/10/2016 12/10/2016 02/11/2017
 
002 (999) OTHER
(FLOOR: 006) MIN 2 20 AMP APPLIANCE CIRCUITS REQ. 219.11 (KITCHEN)
RSLV 12/10/2016 12/10/2016 02/11/2017
 
003 (999) OTHER
(FLOOR: 006) OUTLET BOXES ARE NOT BONDED 250.146 (MC CABLE)
RSLV 12/10/2016 12/10/2016 02/11/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.