BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M378770
Premises: 22 WEST 14 STREET MANHATTAN BIN: 1083516     Block: 577   Lot: 24
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 22 W14 ST Census Tract:   63 Health Area:  5700
14 STREET Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/06/2016 12:51 PM
Application Entered:   03/06/2016 Job Start Date:   03/07/2016
Last Change:   08/22/2025 Job End Date:   03/07/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     05/05/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 012233 Licensee Name: GEORGE OVALLE
Firm: 004102 Firm Name: ARLINGTON ELECL CONTRG IN
Firm Phone: 212-686-5670  Firm Address: 32 EAST 31ST STREET, 8TH FL NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $200.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   DENTAL OFFICE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: DENTAL 360
Authorized Representative:  CATHY JONES
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  2-200 AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  2-200 AMP PANELS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 03/06/2016 Notice: 1 - FIRST NOTICE 05/06/2016
Power Issued: 03/06/2016 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M378770
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/25/2016 04/14/2016 DNM J (30) (0) Y
INSPECTION COMMENTS: NOT A FINAL, INSPECTION .
 
(2) 05/05/2016 05/06/2016 EDB V (55) (3)
INSPECTION COMMENTS: BUILDING HAVE: 3 X 200 A, 3 X 600 A AND 1 X 400 A SERVICE SW(S) TOTAL 2800 A.

OBJECTION FOR APPLICATION #: M378770
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(CELLAR) EXISTING 400 A SER. SW. (NEW TAP).
OPEN 05/05/2016 05/05/2016
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(CELLAR)CONTRACTOR INSTALLED TWO 2ND LEVEL 200 A CB (TAP FROM 400 A SERV.SW.), TOTAL 7 SERV. SW(S).
OPEN 05/05/2016 05/05/2016
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) NO WATER MAIN, NO GND ROD ART. 250
OPEN 05/05/2016 05/05/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.