Electrical Application Details for App #: M378678
Premises: 372 5 AVENUE MANHATTAN BIN: 1015898     Block: 837   Lot: 40
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 372 FIFTH AV Census Tract:   84 Health Area:  5200
APT # 2H Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10018 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 09/15/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/03/2016 2:47 PM
Application Entered:   03/03/2016 Job Start Date:   03/03/2016
Last Change:   09/15/2016 Job End Date:   03/02/2017
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     09/12/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012530 Licensee Name: HEMANCHAL DEONARINE
Firm: 004350 Firm Name: ELPO ELECTRICAL CONTG INC
Firm Phone: 718-384-6700  Firm Address: 50-03 METROPOLITAN AVE, SUITE B QUEENS NY 11385 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $95.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BOBBY SHETH
Owner Business Name: NOT APPLICABLE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1   100 AMPS
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1   #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1   100 AMPS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    18    18  29         
Buildings Total 18    18  29              
Total Units : 78 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/06/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLATION OF NEW 100 AMPS RISER AND NEW 100 AMP CIRCUIT BREAKER PANEL. NEW BRANCH WIRING THROUGHOUT THE APARTMENT.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M378678
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/06/2016 07/06/2016 TUR V (60) (8)
INSPECTION COMMENTS: OBJECTIONS ISSUED ,
 
(2) 09/12/2016 09/13/2016 TUR C R (20) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED, INSPECTION COMPLETE

OBJECTION FOR APPLICATION #: M378678
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 002)110.2(A) DEFECTIVE WIRING LINE VOLTAGE / AND LOW VOLTAGE WIRING INSAME ENCLOSURE
RSLV 07/06/2016 07/06/2016 09/12/2016
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 002)110.2 AMEND 14 AWG USED FOR LINE VOLTAGE CONTROL CIRCUIT FOR FANS
RSLV 07/06/2016 07/06/2016 09/12/2016
 
003 (222) USING NON METALLIC SEALTITE NOT APPROVED
(FLOOR: 002)356.10 AMEND NON METALLIC SEAL TIGHT USED FOR WIRING CONDENSER
RSLV 07/06/2016 07/06/2016 09/12/2016
 
004 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 002)320.40 MC CABLE FEEEDIG THE BLOWERS NOT PROPERLY TERMINATED NOCONNECTOR AND WIRE IS UNDERSIZED AND OVER FUSED AT 30AMP
RSLV 07/06/2016 07/06/2016 09/12/2016
 
005 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
(FLOOR: 002)430.75 AC BLOWERS DO NOT HAVE DISCONNECT SWITCH FOR LINE VOLTAGESIDE
RSLV 07/06/2016 07/06/2016 09/12/2016
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 002)210.8 OUTLETS FEEDING THE TRANSFORMERS FOR BATHROOM LIGHTING MUST BEGFCI PROTECTED IN CASE OF FAILURE OF TRANSFORMER NO WIRING GOINGINTO SHOWER WILL BE ENERGIZED TO 120VOLTS
RSLV 07/06/2016 07/06/2016 09/12/2016
 
007 (999) OTHER
(FLOOR: 002)110.21,22 PANEL MUST BE IDENTIFIED WITH SOURCE OF OCP AND LOCATIONAND VOLTAGE
RSLV 07/06/2016 07/06/2016 09/12/2016
 
008 (999) OTHER
(FLOOR: 002)CANNOT CONFIRM RATING OF THE CONDENSER NEED NAME PLATE RATING
RSLV 07/06/2016 07/06/2016 09/12/2016