| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
100 AMPS |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
#2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
100 AMPS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 002)110.2(A) DEFECTIVE WIRING LINE VOLTAGE / AND LOW VOLTAGE WIRING INSAME ENCLOSURE |
RSLV |
07/06/2016 |
07/06/2016 |
09/12/2016 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 002)110.2 AMEND 14 AWG USED FOR LINE VOLTAGE CONTROL CIRCUIT FOR FANS |
RSLV |
07/06/2016 |
07/06/2016 |
09/12/2016 |
| |
| 003 |
(222) |
USING NON METALLIC SEALTITE NOT APPROVED (FLOOR: 002)356.10 AMEND NON METALLIC SEAL TIGHT USED FOR WIRING CONDENSER |
RSLV |
07/06/2016 |
07/06/2016 |
09/12/2016 |
| |
| 004 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (FLOOR: 002)320.40 MC CABLE FEEEDIG THE BLOWERS NOT PROPERLY TERMINATED NOCONNECTOR AND WIRE IS UNDERSIZED AND OVER FUSED AT 30AMP |
RSLV |
07/06/2016 |
07/06/2016 |
09/12/2016 |
| |
| 005 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED (FLOOR: 002)430.75 AC BLOWERS DO NOT HAVE DISCONNECT SWITCH FOR LINE VOLTAGESIDE |
RSLV |
07/06/2016 |
07/06/2016 |
09/12/2016 |
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 002)210.8 OUTLETS FEEDING THE TRANSFORMERS FOR BATHROOM LIGHTING MUST BEGFCI PROTECTED IN CASE OF FAILURE OF TRANSFORMER NO WIRING GOINGINTO SHOWER WILL BE ENERGIZED TO 120VOLTS |
RSLV |
07/06/2016 |
07/06/2016 |
09/12/2016 |
| |
| 007 |
(999) |
OTHER (FLOOR: 002)110.21,22 PANEL MUST BE IDENTIFIED WITH SOURCE OF OCP AND LOCATIONAND VOLTAGE |
RSLV |
07/06/2016 |
07/06/2016 |
09/12/2016 |
| |
| 008 |
(999) |
OTHER (FLOOR: 002)CANNOT CONFIRM RATING OF THE CONDENSER NEED NAME PLATE RATING |
RSLV |
07/06/2016 |
07/06/2016 |
09/12/2016 |