| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
2 |
2-30A FA |
| B. 101 Up to 200 AMPS |
1 |
1-200A SS4 T-MOBILE |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
3 |
3-1200A SS1,SS2,SS3,FP |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
#10 |
| B. Over #2 to 1/0 |
2 |
#3/0 |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
6 |
#600MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
LP-76 |
| D. 3 Phase Over 225 AMPS |
3 |
DPL-76 DPL-76A DPL-72 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) DPL-72 NO 3 SETS 600 MCM AS SHOWN |
RSLV |
07/09/2016 |
07/09/2016 |
02/21/2017 |
| |
| 002 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) DPL-72B FUSES NO MATCH |
RSLV |
07/09/2016 |
07/09/2016 |
02/21/2017 |
| |
| 003 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) HCP NOT MARKED |
RSLV |
07/09/2016 |
07/09/2016 |
10/06/2016 |
| |
| 004 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) LAYOUT OF SERVICE ROOM DOES NOT MATCH |
RSLV |
07/09/2016 |
07/09/2016 |
02/21/2017 |
| |
| 005 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) DPL-76 FUSES DONT MATCH |
RSLV |
07/09/2016 |
07/09/2016 |
02/21/2017 |
| |
| 006 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) DPL-76A NOT SHOWN ON PRINT |
RSLV |
07/09/2016 |
07/09/2016 |
10/06/2016 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) WATER GROUND NOT BROUGHT TO CT AS SHOWN |
RSLV |
07/09/2016 |
07/09/2016 |
02/21/2017 |
| |
| 008 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) TMOBILE HAS CIRCUIT BREAKER NO FUSE |
RSLV |
07/09/2016 |
07/09/2016 |
02/21/2017 |
| |
| 009 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) FIRE ALARM 30 AM SS NO BOND 250.24 |
RSLV |
07/09/2016 |
07/09/2016 |
02/21/2017 |
| |
| 010 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (BASEMENT) GROUND ROD NOT CONTINUOUS 250.64 |
RSLV |
10/06/2016 |
10/06/2016 |
02/21/2017 |
| |
| 011 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (BASEMENT) FIRE PUMP OVER FUSED 695.4 |
RSLV |
10/06/2016 |
10/06/2016 |
02/21/2017 |
| |
| 012 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) NEW FIRE PUMP SW NOT SHOW ON ONE LINE PRINT |
RSLV |
10/06/2016 |
10/06/2016 |
02/21/2017 |
| |
| 013 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) CONDUCTORS LOAD SIDE OF FIRE PUMP DON'T MATCH DRAWINGS |
RSLV |
10/06/2016 |
10/06/2016 |
02/21/2017 |
| |
| 014 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (BASEMENT) NO GROUND FOR FIRE PUMP 250.66 |
RSLV |
10/06/2016 |
10/06/2016 |
02/21/2017 |
| |
| 015 |
(999) |
OTHER (BASEMENT) GROUND TO COLLECTIVE BAR IMPROPER INSTALLATION 250.64 |
RSLV |
10/06/2016 |
10/06/2016 |
02/21/2017 |
| |
| 016 |
(999) |
OTHER (BASEMENT) FIRE PUMP IN NON FIRE RATED ROOM 695 |
RSLV |
10/06/2016 |
10/06/2016 |
03/07/2017 |
| |
| 017 |
(999) |
OTHER (BASEMENT)200 AMP METER, DISCONNECT SWITCH, FEEDER BELOW FIRE ALARM SWITCHESNOT AS PER DRAWING. AMEND 110.2 |
RSLV |
02/21/2017 |
02/21/2017 |
03/07/2017 |
| |
| 018 |
(999) |
OTHER (BASEMENT)CONDUIT TYPE HOUSING FEEDERS TO FIRE ALARM DISC SWITCH AND FIREALARM CONTROL PANEL NOT AS PER DRAWING. AMEND 1102 |
RSLV |
02/21/2017 |
02/21/2017 |
03/07/2017 |
| |
| 019 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) 200 A SER SW NO MBJ 250.24 |
RSLV |
03/07/2017 |
03/07/2017 |
03/10/2017 |
| |
| 020 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) 200 AMP SER SW NOT GROUNDED PER DRAWING 250.52 |
RSLV |
03/07/2017 |
03/07/2017 |
03/10/2017 |
| |
| 021 |
(999) |
OTHER (BASEMENT) NO MBJ 200 A SW |
RSLV |
03/10/2017 |
03/10/2017 |
03/13/2017 |
| |
| 022 |
(999) |
OTHER (BASEMENT) NO GEC 200 AM SW |
RSLV |
03/10/2017 |
03/10/2017 |
03/13/2017 |