BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M378344
Premises: 41 CHRISTOPHER STREET MANHATTAN BIN: 1010699     Block: 610   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 45 CHRISTOPHER ST Census Tract:   73 Health Area:  6400
6C Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   GROVE STREET,    7 AVENUE SOUTH
Status:   C - JOB IS SIGNED OFF 01/30/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/25/2016 7:41 AM
Application Entered:   02/25/2016 Job Start Date:   02/25/2016
Last Change:   01/30/2018 Job End Date:   06/15/2016
Appointment Status:   
Last Inspection By:   ALGERNON CHARLES       On     01/18/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010523 Licensee Name: VINCENT VERDEROSA
Firm: 001698 Firm Name: SUPER CHARGED ELEC. INC.
Firm Phone: 718-981-7173  Firm Address: 2 DUBOIS AVENUE STATEN ISLAND NY 10310 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $84.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: D TURNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET #6AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  6C  20  12  13  20             
Buildings Total 20  12  13  20                
Total Units : 67 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/21/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING.. EXISTING RISER, REPLACE PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M378344
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/20/2017 11/21/2017 MQY V (50) (3)
INSPECTION COMMENTS: ISSUED OBJECTION
 
(2) 01/18/2018 01/18/2018 AYC C R (60) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M378344
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 006) EXPOSED INCANDESCENT BULB IN CLOTHES CLOSE 410.16
RSLV 11/20/2017 11/20/2017 01/18/2018
 
002 (999) OTHER
(FLOOR: 006) AC BRANCH CIRCUIT NEEDS TO BE AFCI PROTECTED (210.12)
RSLV 11/20/2017 11/20/2017 01/18/2018
 
003 (999) OTHER
(FLOOR: 006)LED DRIVER NOT GROUNDED LIGHTS NOT GROUNDED (NO MECHANICALCONNECTION WITH BX CABLE AND LED DRIVER (110.3)(300.12)
RSLV 11/20/2017 11/20/2017 01/18/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order