BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M378110
Premises: 148 BROADWAY MANHATTAN BIN: 1001087     Block: 64   Lot: 12
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 150 BROADWAY Census Tract:   15.02 Health Area:  7700
18TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Related Job Number:    122659863
DOB Cross Street(s):   LIBERTY STREET,    CORTLANDT STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/18/2016 11:46 AM
Application Entered:   02/18/2016 Job Start Date:   02/19/2016
Last Change:   08/22/2025 Job End Date:   10/10/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     02/15/2017      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 011030 Licensee Name: DEYI LING
Firm: 004259 Firm Name: HV ELECTRIC CORP
Firm Phone: 718-321-8962  Firm Address: 36-17 BUD PLACE FLUSHING NY 11354 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $80.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN POLMA
Authorized Representative:  JOHN POLMA
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
018    60  30    20  60             
Buildings Total 60  30    20  60                
Total Units : 170 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 04/18/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M378110
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/15/2016 04/18/2016 TUR V (55) (23)
INSPECTION COMMENTS: OBJECTIONS ISSUED, INSPECTION NOT COMPLETE MUST CHECK AC WIRING AND CONDUIT, LIBRARY ROOM WIRING, PANTRY WALLS AND CEILINGS, AND FIRE DISCONNECT, AND RISER LOAD FROM BASEMENT
 
(2) 02/15/2017 02/15/2017 TOR J Y (55) (0)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: M378110
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 018)240.3 OVER CURRENT PROTECTION OVERFUSED FOR AC EQUIPMENT 90AMP ON70AMP MAX.
RSLV 04/15/2016 04/15/2016 02/15/2017
 
002 (143) LUMINAIRES NOT PROPERLY SUPPORTED/SECURED
(FLOOR: 018)410.30 LUMINARIES (RECESSED 2X2 LIGHTS) NOT SECURED AS PER CODE TIEDUP WITH #12THHN
OPEN 04/15/2016 04/15/2016
 
003 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(FLOOR: 018)110.2(A) DEFECTIVE LIGHTING IN USE PIG TAILS AND FIXTURES NOTWORKING
OPEN 04/15/2016 04/15/2016
 
004 ( 17) DEFECTIVE SWITCHES ARE IN USE
(FLOOR: 018)110.2(A) DEFECTIVE BREAKER IN USE IN THE PANEL GE PANEL WITGH BRYANTBREAKER
OPEN 04/15/2016 04/15/2016
 
005 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 018) 110.2(A) DEFECTIVE GFCI BY RIGHT OF PANELS
OPEN 04/15/2016 04/15/2016
 
006 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 018)110.2(A) DEFECTIVE WIRING IN USE IN PANELS GROUNDED CONDUCTOR REIDENTIFIED
OPEN 04/15/2016 04/15/2016
 
007 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(FLOOR: 018)320.30 ARMORED CABLES NOT SECURED OVER BLACK IRON IN CEILINGS AND200AMP RATED MC CABLE NOT SECURED IN ELECTRICAL ROOM
OPEN 04/15/2016 04/15/2016
 
008 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 018)320.40 ARMORED CABLES NOT TERMINATED PROPERLY WIRES HANGING WITH NOJ BOXES, AND WIRES IN PANEL ON RIGHT IN 3/4" KO WITH OUT MECHANICALCONTINUITY
OPEN 04/15/2016 04/15/2016
 
009 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 018)314.25 OUTLET BOXES, J, BOXES, LIGHTING BOXES NOT COVERED THRU OUT10-15BOXES
RSLV 04/15/2016 04/15/2016 02/15/2017
 
010 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
(FLOOR: 018)27-3018(B) CONTRACTOR MUST AMMEND HIS APPLICATION TO INCLUDE ALLWIRING, DISCONNECTS, AND PANELS WITH PANELS FEEDERS AND TAP
OPEN 04/15/2016 04/15/2016
 
011 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 018)110.12(A) KNOCKOUTS OPEN IN ALL PANELS, J BOXES , AND BOXES
OPEN 04/15/2016 04/15/2016
 
012 ( 40) LOCKNUTS ARE MISSING OR LOOSE
(FLOOR: 018)300.11 LOCK NUTS LOOSE AND MISSING IN ALL PANELS AND EQUIPMENT
OPEN 04/15/2016 04/15/2016
 
013 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 018)408.4 NO DIRECTORIES IN 2-200AMP MAIN LUG PANELS, AND PANELS IN MAINELECTRIC ROOM ON FLOOR
OPEN 04/15/2016 04/15/2016
 
014 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 018)210.8 GFCI OUTLETS NEEDED 6FT. FROM SINK, AC MECHANICAL ROOMS NOSERVICE GFCI, AND ALL OUTLETS FOR WORK SHOP AREA FOR COUNTERS FORPROTECTION OF PERSONAL
OPEN 04/15/2016 04/15/2016
 
015 (999) OTHER
(FLOOR: 018)110.16 ARCH FLASH LABELS NEEDED ON TWO PANELS , 2-200AMP DISCONNECTSAND AC DISCONNECTS
OPEN 04/15/2016 04/15/2016
 
016 (999) OTHER
(FLOOR: 018)110.21. 110.22, 110.3 ALL PANELS AND DISCONNECTS MUST BE LABELEDWITH DURABLE LABELS (WITH ALL CHARACTERISTICS LISTED IN ARTICLE
OPEN 04/15/2016 04/15/2016
 
017 (999) OTHER
(FLOOR: 018)220 NEED LOAD LETTER FOR THE SPACE, AND FOR THE EXISTING RISERS(NEED TO SEE WHAT SIZE FUSE PROTECTION IS ON THE TWO RISERS THEY ARETAPPING OFF OF FOR THE TWO 200AMP PANELS
OPEN 04/15/2016 04/15/2016
 
018 (999) OTHER
(FLOOR: 018)110.26 ILLUMINATION IS NEEDED IN MAIN ELECTRIC ROOM WHERE PANELSDISCONNECTS ARE LOCATED
OPEN 04/15/2016 04/15/2016
 
019 (999) OTHER
(FLOOR: 018) 210.4 HANDLE TIES AND GROUPING NEEDED IN PANELS
OPEN 04/15/2016 04/15/2016
 
020 (999) OTHER
(FLOOR: 018)250.8 ZIP SCREWS ARE IN USE FOR INSTALLATION OF GROUND LUGS AND BARS
OPEN 04/15/2016 04/15/2016
 
021 (999) OTHER
(FLOOR: 018)320.40 ARMORED CABLES NOT ALL TERMINATED WITH INSULATED BUSHINGS
OPEN 04/15/2016 04/15/2016
 
022 (999) OTHER
(FLOOR: 018)314.16(B) BOX FILL (CEILING ROUND BOXES AND JBOXS FOR OUTLETS ANDSWITCHED OVER FILLED THRU OUT
OPEN 04/15/2016 04/15/2016
 
023 (999) OTHER
(FLOOR: 018)410.56 FLEXIBLE CORD FOR LED LIGHT FIXTURES NEEED PROPER CONNECTORWHEN PASSING THRU CANOPY
OPEN 04/15/2016 04/15/2016