| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (FLOOR: 018)240.3 OVER CURRENT PROTECTION OVERFUSED FOR AC EQUIPMENT 90AMP ON70AMP MAX. |
RSLV |
04/15/2016 |
04/15/2016 |
02/15/2017 |
| |
| 002 |
(143) |
LUMINAIRES NOT PROPERLY SUPPORTED/SECURED (FLOOR: 018)410.30 LUMINARIES (RECESSED 2X2 LIGHTS) NOT SECURED AS PER CODE TIEDUP WITH #12THHN |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 003 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE (FLOOR: 018)110.2(A) DEFECTIVE LIGHTING IN USE PIG TAILS AND FIXTURES NOTWORKING |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 004 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE (FLOOR: 018)110.2(A) DEFECTIVE BREAKER IN USE IN THE PANEL GE PANEL WITGH BRYANTBREAKER |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 005 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (FLOOR: 018) 110.2(A) DEFECTIVE GFCI BY RIGHT OF PANELS |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 006 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 018)110.2(A) DEFECTIVE WIRING IN USE IN PANELS GROUNDED CONDUCTOR REIDENTIFIED |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 007 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (FLOOR: 018)320.30 ARMORED CABLES NOT SECURED OVER BLACK IRON IN CEILINGS AND200AMP RATED MC CABLE NOT SECURED IN ELECTRICAL ROOM |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 008 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (FLOOR: 018)320.40 ARMORED CABLES NOT TERMINATED PROPERLY WIRES HANGING WITH NOJ BOXES, AND WIRES IN PANEL ON RIGHT IN 3/4" KO WITH OUT MECHANICALCONTINUITY |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 009 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 018)314.25 OUTLET BOXES, J, BOXES, LIGHTING BOXES NOT COVERED THRU OUT10-15BOXES |
RSLV |
04/15/2016 |
04/15/2016 |
02/15/2017 |
| |
| 010 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE (FLOOR: 018)27-3018(B) CONTRACTOR MUST AMMEND HIS APPLICATION TO INCLUDE ALLWIRING, DISCONNECTS, AND PANELS WITH PANELS FEEDERS AND TAP |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 011 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 018)110.12(A) KNOCKOUTS OPEN IN ALL PANELS, J BOXES , AND BOXES |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 012 |
( 40) |
LOCKNUTS ARE MISSING OR LOOSE (FLOOR: 018)300.11 LOCK NUTS LOOSE AND MISSING IN ALL PANELS AND EQUIPMENT |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 013 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 018)408.4 NO DIRECTORIES IN 2-200AMP MAIN LUG PANELS, AND PANELS IN MAINELECTRIC ROOM ON FLOOR |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 014 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 018)210.8 GFCI OUTLETS NEEDED 6FT. FROM SINK, AC MECHANICAL ROOMS NOSERVICE GFCI, AND ALL OUTLETS FOR WORK SHOP AREA FOR COUNTERS FORPROTECTION OF PERSONAL |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 015 |
(999) |
OTHER (FLOOR: 018)110.16 ARCH FLASH LABELS NEEDED ON TWO PANELS , 2-200AMP DISCONNECTSAND AC DISCONNECTS |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 016 |
(999) |
OTHER (FLOOR: 018)110.21. 110.22, 110.3 ALL PANELS AND DISCONNECTS MUST BE LABELEDWITH DURABLE LABELS (WITH ALL CHARACTERISTICS LISTED IN ARTICLE |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 017 |
(999) |
OTHER (FLOOR: 018)220 NEED LOAD LETTER FOR THE SPACE, AND FOR THE EXISTING RISERS(NEED TO SEE WHAT SIZE FUSE PROTECTION IS ON THE TWO RISERS THEY ARETAPPING OFF OF FOR THE TWO 200AMP PANELS |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 018 |
(999) |
OTHER (FLOOR: 018)110.26 ILLUMINATION IS NEEDED IN MAIN ELECTRIC ROOM WHERE PANELSDISCONNECTS ARE LOCATED |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 019 |
(999) |
OTHER (FLOOR: 018) 210.4 HANDLE TIES AND GROUPING NEEDED IN PANELS |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 020 |
(999) |
OTHER (FLOOR: 018)250.8 ZIP SCREWS ARE IN USE FOR INSTALLATION OF GROUND LUGS AND BARS |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 021 |
(999) |
OTHER (FLOOR: 018)320.40 ARMORED CABLES NOT ALL TERMINATED WITH INSULATED BUSHINGS |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 022 |
(999) |
OTHER (FLOOR: 018)314.16(B) BOX FILL (CEILING ROUND BOXES AND JBOXS FOR OUTLETS ANDSWITCHED OVER FILLED THRU OUT |
OPEN |
04/15/2016 |
04/15/2016 |
|
| |
| 023 |
(999) |
OTHER (FLOOR: 018)410.56 FLEXIBLE CORD FOR LED LIGHT FIXTURES NEEED PROPER CONNECTORWHEN PASSING THRU CANOPY |
OPEN |
04/15/2016 |
04/15/2016 |
|