Electrical Application Details for App #: M377845
Premises: 383 LAFAYETTE STREET MANHATTAN BIN: 1008512     Block: 531   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 383 LAFAYETTE ST Census Tract:   55.02
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Special Place Name:   NYU
DOB Cross Street(s):   GREAT JONES STREET,    EAST 4 STREET
Status:   C - JOB IS SIGNED OFF 01/19/2021
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   02/10/2016 Job Start Date:   02/28/2016
Last Change:   01/19/2021 Job End Date:   05/28/2016
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     01/19/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012411 Licensee Name: CHRISTOPHER W SCALA
Firm: 000898 Firm Name: LOWY & DONNATH INC.
Firm Phone: 718-392-8222  Firm Address: 10-37 49TH AVENUE LONG ISLAND CITY NY 11101 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
010517 SCALA, JR., ANTHONY J 000898 LOWY & DONNATH INC. RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $565.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53189     Submittal #: 14A0626  
Owner / Occup: SEAN KELLY
Owner Business Name: NYU
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1-3000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  8 SETS OF 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/10/2016 Notice: 1 - FIRST NOTICE 03/03/2020
Power Issued: 02/10/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NYU 383 LAFAYETTE-ADVISORY BOARD

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M377845
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/03/2020 03/03/2020 MJD V (60) (6)
INSPECTION COMMENTS: FAIL, OBJECTIONS ISSUED
 
(2) 11/07/2020 11/09/2020 CDX C R (90) (0)
INSPECTION COMMENTS: PASS. PLAN REVIEW CAL# 53189/ SUB# 14A0626 REV: 3-4-5
 
(3) 01/19/2021 01/19/2021 TOR C (30) (0) Y
INSPECTION COMMENTS: PASS.

OBJECTION FOR APPLICATION #: M377845
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT)ART. 250.102 BONDING JUMPERS NOT INSTALLED ALL LOAD SIDE CONDUITS
RSLV 03/03/2020 03/03/2020 11/07/2020
 
002 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(BASEMENT) ART. 250.24 3000 AMP SECOND FUSE DISCONNECT SWITCH
RSLV 03/03/2020 03/03/2020 11/07/2020
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) ART. 250 SERVICE NOT PROPERLY GROUNDED
RSLV 03/03/2020 03/03/2020 11/07/2020
 
004 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)110.2 FUSE SIZES AND BUCKET SWITCH LOCATIONS NOT AS PER APPROVEDDRAWING
RSLV 03/03/2020 03/03/2020 11/07/2020
 
005 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
(BASEMENT)TABLE 250.122 3000 AMP FEEDER GROUND CONDUCTORS UNDERSIZED
RSLV 03/03/2020 03/03/2020 11/07/2020
 
006 (999) OTHER
(BASEMENT)CONTRACTOR NEEDS TO CORRECT APPLICATION, SERVICE SWITCHES, FEEDERS,PANELS, FIRE PUMP
RSLV 03/03/2020 03/03/2020 11/07/2020