| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
125 AMPS |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 012)314.25 TWO GANG BOX IN CLOSET WITH SWITCH BANKS NOT COVERED |
RSLV |
04/13/2017 |
04/13/2017 |
06/22/2017 |
| |
| 002 |
( 31) |
MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN OUTLET BOX (FLOOR: 012)314.16 OUTLET ON KITCHEN COUNTER AND ALL OUTLETS THAT LOOP IN ANDOUT UNDERSIZED SEE BOX FILL CHART 2.5INCH BOX |
RSLV |
04/13/2017 |
04/13/2017 |
06/22/2017 |
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 012) 408.4 COMPLETED DIRECTORY INSTALLED |
RSLV |
04/13/2017 |
04/13/2017 |
07/06/2017 |
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 012)210.8 DEFECTIVE GFCI IN GUEST BATHROOM MIRROR GFCI KEEPS TRIPPINGNOT RESETTING |
RSLV |
04/13/2017 |
04/13/2017 |
06/22/2017 |
| |
| 005 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 012)210.8, 110.2 PER MANUFACTURES TOWEL WARMERS HOT INSTALLED WITH GFCIPROTECTION CKT 33 FOR GUEST AND MASTER BATHROOM |
RSLV |
04/13/2017 |
04/13/2017 |
07/06/2017 |
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 012)210.8 MIRROR IN SHOWER IS CONTROLLED BY TRANSFORMER MUST HAVE GFCIPROTECTING THE LINE SIDE OF THE CIRCUIT INSTALLED IN SHOWERENCLOSURE MASTER BATH |
RSLV |
04/13/2017 |
04/13/2017 |
06/22/2017 |
| |
| 007 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 012)210.12(B) COULD NOT CONFIRM ALL AREAS FOR AFCI AT TIME OF INSPECTIONDIRECTORY NOT INSTALLED |
RSLV |
04/13/2017 |
04/13/2017 |
07/06/2017 |
| |
| 008 |
(999) |
OTHER (FLOOR: 012)250.112 AC DISCONNECTS AND BREAKER ENCLOSURES NOT GROUNDED MC CABLE |
RSLV |
04/13/2017 |
04/13/2017 |
06/22/2017 |
| |
| 009 |
(999) |
OTHER (FLOOR: 012)250.8 (A) (1-8) ISOLATED NEUTRAL BARS AND GROUND LUG NOT INSTALLEDWITH MACHINE THREADED SCREW |
RSLV |
04/13/2017 |
04/13/2017 |
06/22/2017 |
| |
| 010 |
(999) |
OTHER (FLOOR: 012) KITCHEN MISSING GFCI 210.8 |
RSLV |
06/22/2017 |
06/22/2017 |
07/06/2017 |
| |
| 011 |
(999) |
OTHER (FLOOR: 012) OUTLET BOXES NOT BOND AS PER ART. 250.8 |
RSLV |
06/22/2017 |
06/22/2017 |
07/06/2017 |
| |
| 012 |
(999) |
OTHER (FLOOR: 012) BATH ROOMS MC CABLE OUTLET BOXES ARE NOT BONDED 250.146 |
RSLV |
06/22/2017 |
06/22/2017 |
07/06/2017 |