BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M376521
Premises: 6 PARK AVENUE MANHATTAN BIN: 1017105     Block: 864   Lot: 35
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 10 PARK AV Census Tract:   74 Health Area:  5200
21A Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):   EAST 34 STREET,    EAST 35 STREET
Status:   C - JOB IS SIGNED OFF 06/09/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/05/2016 6:01 PM
Application Entered:   01/05/2016 Job Start Date:   01/05/2016
Last Change:   06/09/2016 Job End Date:   06/10/2016
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     06/09/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012657 Licensee Name: ANTON NICAJ
Firm: 004495 Firm Name: ALL CITY ELECTRICAL INC
Firm Phone: 718-392-3200  Firm Address: 44-15 BARNETT AVENUE SUNNYSIDE NY 11104 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LES SUMNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12 CIRCUIT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
021  21A                 
Buildings Total                   
Total Units : 8 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/25/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACE PANEL AND UPGRADE KITCHEN

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M376521
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/25/2016 05/25/2016 STP V (30) (3)
INSPECTION COMMENTS: FAIL.
 
(2) 06/09/2016 06/09/2016 CBK C R (40) (0)
INSPECTION COMMENTS: #10 FEED IS EXISTING IN THE BUILDING.

OBJECTION FOR APPLICATION #: M376521
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 021) PANEL FED WITH # 10AWG IN DWELLING 215.2 LOCAL LAW.
RSLV 05/25/2016 05/25/2016 06/09/2016
 
002 (999) OTHER
(FLOOR: 021) NO TR RECEPTACLES IN KICTHEN 406.11
RSLV 05/25/2016 05/25/2016 06/09/2016
 
003 (999) OTHER
(FLOOR: 021) CABINET RECEPTACLE IN WOOD NO EXTENDER 314.20
RSLV 05/25/2016 05/25/2016 06/09/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back