BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M376515
Premises: 1041 PARK AVENUE MANHATTAN BIN: 1047951     Block: 1515   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1045 PARK AVE. Census Tract:   148.02 Health Area:  3600
13 A/B Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 86 STREET,    EAST 87 STREET
Status:   C - JOB IS SIGNED OFF 02/20/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/05/2016 3:59 PM
Application Entered:   01/05/2016 Job Start Date:   01/05/2016
Last Change:   02/20/2018 Job End Date:   01/05/2017
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     02/20/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011175 Licensee Name: DONALD MCGEACHY
Firm: 000436 Firm Name: DONALD MCGEACHY, INC.
Firm Phone: 212-249-0999  Firm Address: 502A EAST 84 STREET NEW YORK NY 10028 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $86.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DANIEL & NICKY SHATZ
Owner Business Name: 1045 PARK AVE OWNERS CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
013  A/B  27  37  10  40  80             
Buildings Total 27  37  10  40  80                
Total Units : 194 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 12/13/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M376515
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/02/2017 10/02/2017 PHG V (40) (5)
INSPECTION COMMENTS: CONTRACTOR TO FIX APP TO REFLECT ALL WORK FEEDERS PANELS MOTORS HEATERS ECT. DID NOT SEE MAIN FUSE IN BSMT. CONTRACTOR TO PROVIDED CUT SHEET FOR ALL CLOSETS WITH FLEX CORD NO CONNECTOR
 
(2) 12/12/2017 12/13/2017 PHG J X (35) (0) Y
INSPECTION COMMENTS: OBJECTIONS DO NOT SHOW ON ACELLA SYSTEM. CONTRACTOR TO CLAIM ALL WORK DONE IN APT. CLOSET LIGHT CHANGED PICTURE LIGHTS TAKEN DOWN IN WINE RM. BATHRM OUTLET ADDED. CONTRACTOR STATED RISER WAS EXISTING NO APP ON FILE FOR 13A/B RISER DID NOT INSPECT RISER OR WORK NOT FILED FOR
 
(3) 02/20/2018 02/20/2018 MLF C R (24) (0)
INSPECTION COMMENTS: PASS ALL OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M376515
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(FLOOR: 013) FLEX CORD PASSED BEHING WALLS IN WINE CELLAR 400.8
RSLV 10/02/2017 10/02/2017 02/20/2018
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 013)CONTRACTOR TO PROVIDE INFO FOR CLOSET LIGHT FLEX CORD 110.3
RSLV 10/02/2017 10/02/2017 02/20/2018
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 013)ALL PICTURE LIGHTS NO GROUND PROVIDED FOR FLEX CORD 250.122
RSLV 10/02/2017 10/02/2017 02/20/2018
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 013) NO AFCI IN NEEDED AREAS 210.12
RSLV 10/02/2017 10/02/2017 02/20/2018
 
005 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(FLOOR: 013) MISSING OUTLET IN MASTER BATH 210.52
RSLV 10/02/2017 10/02/2017 02/20/2018