| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
24C |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 001)210.8 COMMERCIAL KITCHEN ALL OUTLETS MUST BE GFCI PROTECTED ,FEEDING EQUIPMENT AND WITH IN 6FT. OF WATER (SINK) |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 002 |
(999) |
OTHER (FLOOR: 001) 314.20 OUTLETS SET BACK IN TILE AND WOOD SURFACES |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 003 |
(999) |
OTHER (FLOOR: 001) 220.14G SHOW WINDOW CIRCUIT |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 004 |
(999) |
OTHER (FLOOR: 001)600.5 EACH COMMERCIAL SPACE MUJST HAVE A DEDICATED SIGN CIRCUIT |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 005 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT)110.2(A) DEFECTIVE BURNT WIRE NEEDS TO BE REMOVED WAS SHORTED BYSOMEONE DAMAGING CONDUIT ON ROOF |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 006 |
(999) |
OTHER (BASEMENT)110.3, 110.21, 110.22 ALL PANELS AND DISCONNECTS MUST BE IDENTIFIEDWITH DURABLE MEANS ALL CHARACTERISTICS IN THE AFOREMENTIONED CODEREF. |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 007 |
(999) |
OTHER (BASEMENT)110.16 ARCH FLASH LABELS FOR ALL PANELS, DISCONNECTS, AND METERS |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 008 |
(999) |
OTHER (BASEMENT) 250.8 NO ZIOP SCREWS FOR GROUND LUGS |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 009 |
(999) |
OTHER (ROOF) 210.63 GFCI MUST BE FED BY SAME TENANT OR LAND LORD |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |