| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
|
| B. Over #2 to 1/0 |
1 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
|
| D. 3 Phase Over 225 AMPS |
1 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
1 HANDICAP LIFT |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 001)OUTLETS NOT GFI PROTECTED WITH IN 6' FROM SINK (BAR AND MAIN LOBBY)ART. 210.8 |
RSLV |
03/20/2018 |
03/20/2018 |
06/24/2019 |
| |
| 002 |
(999) |
OTHER (FLOOR: 001)OUTLETS SET BACK IN COMBUSTIBLE MATERIALS T-OUT ART. 314.20 |
RSLV |
03/20/2018 |
03/20/2018 |
06/24/2019 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS) ARC FLASH LABELS NOT PROVIDED T-OUT ART. 110.16 |
RSLV |
03/20/2018 |
03/20/2018 |
06/24/2019 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)OVERCURRENT PROTECTION NOT AS PER MANUFACTORY REQUIREMENTS ART.100.2 |
RSLV |
03/20/2018 |
03/20/2018 |
06/24/2019 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) OPEN KNOCKOUTS T-OUT ART. 110.12A |
RSLV |
03/20/2018 |
03/20/2018 |
06/24/2019 |
| |
| 006 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (CELLAR) T-OUT |
RSLV |
03/20/2018 |
03/20/2018 |
06/24/2019 |
| |
| 007 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT (CELLAR) OUTSIDE UNITS |
RSLV |
03/20/2018 |
03/20/2018 |
06/24/2019 |