BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M376033
Premises: 301 EAST 40 STREET MANHATTAN BIN: 1038645     Block: 1333   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 305 E40TH ST Census Tract:   88 Health Area:  5000
APT 14D, 14TH FL Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):    2 AVENUE,    QUEENS MIDTOWN TUNNEL APPROACH
Status:   C - JOB IS SIGNED OFF 07/13/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/16/2015 12:14 PM
Application Entered:   12/16/2015 Job Start Date:   12/16/2015
Last Change:   07/13/2016 Job End Date:   12/16/2016
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     07/11/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009745 Licensee Name: LOUIS DEMICHELE
Firm: 002678 Firm Name: ALL AROUND ELECTRIC CORP.
Firm Phone: 347-987-3556  Firm Address: 168 49TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $63.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MEREDITH POLONSKY
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
014  14D  10  16    10             
Buildings Total 10  16    10                
Total Units : 44 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/16/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M376033
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/16/2016 06/16/2016 CBK V (43) (4)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(2) 07/11/2016 07/12/2016 STP C R (30) (0)
INSPECTION COMMENTS: PASS VIOLATIONS REMOVED.

OBJECTION FOR APPLICATION #: M376033
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 014) MC GREEN WIRE USED AS NEUTRAL IN PANEL
RSLV 06/16/2016 06/16/2016 07/11/2016
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 014)BOXES NOT COVERED IN MASTER BATH RM. AND KIDS RM CLOSET.
RSLV 06/16/2016 06/16/2016 07/11/2016
 
003 (999) OTHER
(FLOOR: 014) DRIVERS FOR KITCHEN UNDER CAB LIGHTS NOT ACCESSIBLE.
RSLV 06/16/2016 06/16/2016 07/11/2016
 
004 (999) OTHER
(FLOOR: 014) RECEPTACLE BOXES SET BACK MORE THAN 1/4" IN KITCHEN.
RSLV 06/16/2016 06/16/2016 07/11/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.