Electrical Application Details for App #: M375579
Premises: 135 FULTON STREET MANHATTAN BIN: 1001242     Block: 89   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 139 FULTON ST Census Tract:   15.01
BSMT Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Special Place Name:   T-MOBILE
DOB Cross Street(s):   NASSAU STREET,    BROADWAY
Status:   C - JOB IS SIGNED OFF 03/24/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/05/2015 Job Start Date:   11/30/2015
Last Change:   03/24/2017 Job End Date:   12/31/2015
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     03/23/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012748 Licensee Name: EDWARD C CUFF
Firm: 004588 Firm Name: E.C. ELECL CONTRACTOR INC
Firm Phone: 718-231-0574  Firm Address: 27 EAST 233RD STREET BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $115.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RONALD MOORE
Owner Business Name: T-MOBILE
Authorized Representative:  EDWARD CUFF
Relationship To Owner:   RR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  (3) 3/0 THHN 1-#2 GROUND
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/05/2015 Notice: 1 - FIRST NOTICE 01/23/2017
Power Issued: 12/05/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING OF CELL SITE EQUIPMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M375579
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/24/2016 08/25/2016 MQY J (49) (0) Y
INSPECTION COMMENTS: NOT READY FOR INSPECTION. NEEDS TO BRING A HELPER TO REMOVE DOORS OF DP TO INSPECT TAP. FULL INSPECTION NEEDED
 
(2) 01/23/2017 01/23/2017 CBK V (45) (3)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(3) 03/23/2017 03/24/2017 BUR C R (45) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED

OBJECTION FOR APPLICATION #: M375579
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(BASEMENT)SECOND LEVEL 200A TAP ON BAR IN MDP FED FROM 5000A SERVICE.
RSLV 01/23/2017 01/23/2017 03/23/2017
 
002 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(BASEMENT) TAP CONDUCTOR. TAPPED IN PULL BOX TO FEED 30 AMP DISC.
RSLV 01/23/2017 01/23/2017 03/23/2017
 
003 (999) OTHER
(BASEMENT) DOUBLE UP ON LUG IN 200A DISC. SWITCH. 110.3
RSLV 01/23/2017 01/23/2017 03/23/2017