BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M375127
Premises: 202 CANAL STREET MANHATTAN BIN: 1082488     Block: 200   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 202 CANAL ST Census Tract:   29 Health Area:  7700
3FL Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   103
DOB Cross Street(s):   MOTT STREET,    MULBERRY STREET
Status:   C - JOB IS SIGNED OFF 04/26/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/20/2015 9:57 AM
Application Entered:   11/20/2015 Job Start Date:   11/21/2015
Last Change:   04/26/2016 Job End Date:   11/19/2016
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     04/25/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011769 Licensee Name: ZHENG LI
Firm: 003451 Firm Name: KJK ELECTRIC INC
Firm Phone: 917-682-3886  Firm Address: 79 BRIDGEWATER STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $52.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID KHAZZAM
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  305  25  22    12               
Buildings Total 25  22    12                  
Total Units : 59 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/28/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING FOR NEW COMMERCIAL SPACE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M375127
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/16/2016 03/16/2016 TOR N (30) (0) Y
INSPECTION COMMENTS: NO ACCESS TO SPACE.
 
(2) 03/25/2016 03/28/2016 STP V (45) (3)
INSPECTION COMMENTS: FAIL. PANEL EXISTING STATED ONLY BRANCH CKT WIRING DONE.
 
(3) 04/25/2016 04/26/2016 BUR C R (35) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED

OBJECTION FOR APPLICATION #: M375127
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 003) FLEX CORD IN CEILING FOR LED XFRMER 400.8
RSLV 03/25/2016 03/25/2016 04/25/2016
 
002 (999) OTHER
(FLOOR: 003) KO NOT CLOSED IN A.C DISCONNECT SWITCH 110.12
RSLV 03/25/2016 03/25/2016 04/25/2016
 
003 (999) OTHER
(FLOOR: 003) A.C. DISCONNECT SWITCH NOT GROUNDED 250.4
RSLV 03/25/2016 03/25/2016 04/25/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back