Electrical Application Details for App #: M374958
Premises: 125 EAST 72 STREET MANHATTAN BIN: 1042844     Block: 1407   Lot: 16
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 125 E 72 ST Census Tract:   128 Health Area:  4100
APT 13A Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   PARK AVENUE,    LEXINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 12/23/2016 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/17/2015 8:17 PM
Application Entered:   11/17/2015 Job Start Date:   11/17/2015
Last Change:   12/23/2016 Job End Date:   09/17/2016
Appointment Status:   
Last Inspection By:   URIM SYLA       On     06/08/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011485 Licensee Name: BENJAMIN DREBIN
Firm: 002950 Firm Name: ACCURATE ELEC'L CORP.
Firm Phone: 718-606-9181  Firm Address: 11-07 43RD ROAD LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES GRANT
Owner Business Name: JAMES GRANT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
013  13A                   
Buildings Total                     
Total Units : 8 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 05/03/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  D1U2K3E4- APT 13A KITCHEN, HALL, BATH

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M374958
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/10/2016 03/11/2016 PHG N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 04/06/2016 04/07/2016 TUR V (55) (10)
INSPECTION COMMENTS: OBJECTIONS ISSUED, INSPECTION COMPLETE
 
(3) 05/02/2016 05/03/2016 UMS V X (45) (4)
INSPECTION COMMENTS: CONTRACTOR ADMITTED SMALL PANEL BELOW EXISTING WAS INSTALLED BY HIM. PANEL HAS BEEN ADDED TO APP. EXISTING OBJECTIONS ARE STILL OPEN
 
(4) 06/08/2016 06/09/2016 UMS C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. PANEL THAT WAS ADDED ON THE LAST INSPECTION NOT INSTALLED BY CONTRACTOR. ELECTRICAL PLAN SHOWED THAT BOTH PANELS WERE EXISTING. PLAN PROVIDED BY GC AND ELECTRICIAN

OBJECTION FOR APPLICATION #: M374958
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 013)110.2(A) 220VOLT LINE FROM MAIN PANEL CIRCUIT 17,19 TO 220VOLTOUTLET ON THE KITCHEN COUNTER THE WIRES ARE DAMAGED IN BOX ONCOUNTER AND THE WIRES ARE IN THE SAME ASSEMBLY OF CIRCUIT FOUR 12/3NOT DESIGNED FOR THIS TYPE OF INSTALL
RSLV 04/06/2016 04/06/2016 06/08/2016
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 013) 110.2(A) CIRCUIT 4 MAIN PANEL NO NEUTRAL
RSLV 04/06/2016 04/06/2016 06/08/2016
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 013)110.2(A) ALL KITCHEN AREA AND WET BAR OUTLETS SET TO FAR BACK OVERONE INCH SET BACK NEEDS GROUNDING TAIL
RSLV 04/06/2016 04/06/2016 06/08/2016
 
004 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(FLOOR: 013)300.3(B) CIRCUIT 4 IN MAIN PANEL NUETRAL NOT IN SAME ASSEMBLY BEINGBACK FEED FROM SOME WHERE ELSE
RSLV 04/06/2016 04/06/2016 06/08/2016
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 013)314.25 J BOX IN THE CEILING OF ELECTRICAL CLOSET NOT CLOSED
RSLV 04/06/2016 04/06/2016 06/08/2016
 
006 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 013) 110.12(A) KO SEALS IN BOTH PANELS NOT CLOSED
RSLV 04/06/2016 04/06/2016 06/08/2016
 
007 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 013)408.4 DIRECTORY IN BOTH PANELS NEEDS TO BE UPDATED DUE TO NEW WIRING
RSLV 04/06/2016 04/06/2016 06/08/2016
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 013)210. 220VOLT LINE ON KITCHEN COUNTER MUST PUT GFCI PROTECTION
RSLV 04/06/2016 04/06/2016 06/08/2016
 
009 (999) OTHER
(FLOOR: 013)314.20 ALL DEVICES IN KITCHEN AND WET BAR AREA SPLASH SET BECK NEEDSADAPTERS
RSLV 04/06/2016 04/06/2016 06/08/2016
 
010 (999) OTHER
(FLOOR: 013)210.12 AFCI NEEDED FOR AREAS REWIRED KITCHEN LIGHTS , HALL LIGHTSAND OUTLETS
RSLV 04/06/2016 04/06/2016 06/08/2016
 
011 (999) OTHER
(FLOOR: 013)INTERNAL BUS BAR FRAME OF SMALL PANEL IS DAMAGED. NEC 110.12B
RSLV 05/02/2016 05/02/2016 06/08/2016
 
012 (999) OTHER
(FLOOR: 013)NO HANDLE TIES PROVIDED FOR MULTIWIRE BRANCH CIRCUITS. NEC 210.4
RSLV 05/02/2016 05/02/2016 06/08/2016
 
013 (999) OTHER
(FLOOR: 013)BRANCH CIRCUITS NOT GROUNDED PROPERLY. GROUNDING CONDUCTORS NOTGROUNDED ANYWHERE IN PANEL. NEC 210
RSLV 05/02/2016 05/02/2016 06/08/2016
 
014 (999) OTHER
(FLOOR: 013)BRANCH CIRCUIT CONDUCTORS NOT IDENTIFIED PROPERLY. NEC 200.6
RSLV 05/02/2016 05/02/2016 06/08/2016