| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
1 |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 013)110.2(A) 220VOLT LINE FROM MAIN PANEL CIRCUIT 17,19 TO 220VOLTOUTLET ON THE KITCHEN COUNTER THE WIRES ARE DAMAGED IN BOX ONCOUNTER AND THE WIRES ARE IN THE SAME ASSEMBLY OF CIRCUIT FOUR 12/3NOT DESIGNED FOR THIS TYPE OF INSTALL |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 013) 110.2(A) CIRCUIT 4 MAIN PANEL NO NEUTRAL |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 013)110.2(A) ALL KITCHEN AREA AND WET BAR OUTLETS SET TO FAR BACK OVERONE INCH SET BACK NEEDS GROUNDING TAIL |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 004 |
(243) |
CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED (FLOOR: 013)300.3(B) CIRCUIT 4 IN MAIN PANEL NUETRAL NOT IN SAME ASSEMBLY BEINGBACK FEED FROM SOME WHERE ELSE |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 005 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 013)314.25 J BOX IN THE CEILING OF ELECTRICAL CLOSET NOT CLOSED |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 006 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 013) 110.12(A) KO SEALS IN BOTH PANELS NOT CLOSED |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 007 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 013)408.4 DIRECTORY IN BOTH PANELS NEEDS TO BE UPDATED DUE TO NEW WIRING |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 008 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 013)210. 220VOLT LINE ON KITCHEN COUNTER MUST PUT GFCI PROTECTION |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 009 |
(999) |
OTHER (FLOOR: 013)314.20 ALL DEVICES IN KITCHEN AND WET BAR AREA SPLASH SET BECK NEEDSADAPTERS |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 010 |
(999) |
OTHER (FLOOR: 013)210.12 AFCI NEEDED FOR AREAS REWIRED KITCHEN LIGHTS , HALL LIGHTSAND OUTLETS |
RSLV |
04/06/2016 |
04/06/2016 |
06/08/2016 |
| |
| 011 |
(999) |
OTHER (FLOOR: 013)INTERNAL BUS BAR FRAME OF SMALL PANEL IS DAMAGED. NEC 110.12B |
RSLV |
05/02/2016 |
05/02/2016 |
06/08/2016 |
| |
| 012 |
(999) |
OTHER (FLOOR: 013)NO HANDLE TIES PROVIDED FOR MULTIWIRE BRANCH CIRCUITS. NEC 210.4 |
RSLV |
05/02/2016 |
05/02/2016 |
06/08/2016 |
| |
| 013 |
(999) |
OTHER (FLOOR: 013)BRANCH CIRCUITS NOT GROUNDED PROPERLY. GROUNDING CONDUCTORS NOTGROUNDED ANYWHERE IN PANEL. NEC 210 |
RSLV |
05/02/2016 |
05/02/2016 |
06/08/2016 |
| |
| 014 |
(999) |
OTHER (FLOOR: 013)BRANCH CIRCUIT CONDUCTORS NOT IDENTIFIED PROPERLY. NEC 200.6 |
RSLV |
05/02/2016 |
05/02/2016 |
06/08/2016 |