BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M374829
Premises: 626 5 AVENUE MANHATTAN BIN: 1083860     Block: 1266   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 630 5 AV Census Tract:   104 Health Area:  4800
34TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10111 Community Board:   105
Special Place Name:   PHASE 1
DOB Cross Street(s):   EAST 50 STREET,    EAST 51 STREET
Status:   C - JOB IS SIGNED OFF 03/04/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/13/2015 2:04 PM
Application Entered:   11/13/2015 Job Start Date:   11/13/2015
Last Change:   03/04/2016 Job End Date:   11/30/2015
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     03/03/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011809 Licensee Name: ARTHUR GROSSMAN
Firm: 000176 Firm Name: ATLAS-ACON ELEC. SERVICE
Firm Phone: 212-741-0600  Firm Address: 283 HUDSON STREET NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $296.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: RCPI LANDMARK PROPERTIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  4-#3
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  100 AMP 42 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
034    189  115    20  189         
Buildings Total 189  115    20  189              
Total Units : 514 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/21/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M374829
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/30/2015 12/03/2015 NRS Z (0) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELED APPOINTMENT
 
(2) 12/18/2015 12/21/2015 TUR V (50) (4)
INSPECTION COMMENTS: ISSUED OBJECTIONS FOR PHASE ONE AND TWO
 
(3) 03/03/2016 03/04/2016 STP C R (30) (0)
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M374829
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 034) 110.16 NO ARCH FLASH LABELS
RSLV 12/18/2015 12/18/2015 03/03/2016
 
002 (999) OTHER
(FLOOR: 034) 210.4 GROUPING AND HANDLE TIES FOR PANELS
RSLV 12/18/2015 12/18/2015 03/03/2016
 
003 (999) OTHER
(FLOOR: 034)110.2 PVC TIME CLOCK IN USE NO GROUNDING FOR THE ELECTRIC IN CLOCK
RSLV 12/18/2015 12/18/2015 03/03/2016
 
004 (999) OTHER
(FLOOR: 034) 314.4 FURNITURE BOX NOT BONDED
RSLV 12/18/2015 12/18/2015 03/03/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.