BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M374757
Premises: 185 MOTT STREET MANHATTAN BIN: 1007186     Block: 480   Lot: 33
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 58 KENMARE ST Census Tract:   41 Health Area:  6800
BASTMENT AND 1 FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   MOTT STREET,    MULBERRY STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/12/2015 8:07 AM
Application Entered:   11/12/2015 Job Start Date:   11/12/2015
Last Change:   08/22/2025 Job End Date:   03/12/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     06/17/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010939 Licensee Name: MICHAEL L ALPHONSE
Firm: 002249 Firm Name: BESTCO GENERAL ELEC. MAIN
Firm Phone: 718-324-5582  Firm Address: 922 EAST 233RD STREET BRONX NY 10466 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (4  Stores, 15 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARC COKEN
Authorized Representative:  MARC COKEN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  200AMP. 3-PHASE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  SET - 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  200AMP. 3- PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                         
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 0
Existing Meters 19 + New Meters 2 - Removed Meters 0 = Total Meters 21

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 11/12/2015 Notice: 1 - FIRST NOTICE 06/21/2016
Power Issued: 11/12/2015 Response:  

Follow-Up:
Contractor's Comments:  INSTALLING 2-200AMP.4 WIRE METER,2-200AMP.3 PHASE S/SWITCH,2-200AMP.PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M374757
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/17/2016 06/21/2016 EDB V (60) (3)
INSPECTION COMMENTS: NO ACCESS TO NEW 200 A SW. NOT FINAL.

OBJECTION FOR APPLICATION #: M374757
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR)NOT APPROVED CONNECTION IN USE FOR POWER OF NEW 200 A SW.(S).
OPEN 06/17/2016 06/17/2016
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) DEFECTIVE METER SOCKET IN USE 110.2,3
OPEN 06/17/2016 06/17/2016
 
003 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
(CELLAR) EXISTING CONNECTION BOX OVERFILL
OPEN 06/17/2016 06/17/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.